User’s Manual
25
3.5 T
YPICAL
C
ONFIGURATIONS
The diagrams shown in Figures 3-9, 3-10, 3-11 illustrate typical connections of a
M3645P unit with generic VFDs. There are many other configurations that may be
applied, providing basic connection criteria are maintained, including:
•
The AC terminals should have a low impedance path back to the grid.
•
No reactors should be connected upstream of the unit without consulting Bonitron
for instructions.
•
The AC feed to the VFDs should be left disconnected.
•
The DC terminals should be connected to a fixed bus of one or more VFDs. This
should never be connected to a switching source such as the braking resistor
terminals on some drives.
•
The DC terminals should not be connected to an active front end drive without
instructions from Bonitron.
Содержание M3645P
Страница 14: ...M3645P 14 This page intentionally left blank ...
Страница 22: ...M3645P 22 Figure 3 5 M3645P 150A 225A and 300A Connection Locations ...
Страница 27: ...User s Manual 27 Figure 3 9 M3645P 150A 225A and 300A Power Wiring ...
Страница 30: ...M3645P 30 This page intentionally left blank ...
Страница 44: ...M3645P 44 6 6 DIMENSIONS AND MECHANICAL DRAWINGS Figure 6 1 M3645P M10 Chassis Dimensional Outline ...
Страница 45: ...User s Manual 45 Figure 6 2 M3645P M11 Chassis Dimensional Outline ...
Страница 46: ...M3645P 46 Figure 6 3 M3645P M12 Chassis Dimensional Outline ...
Страница 47: ...User s Manual 47 Figure 6 4 M3645P M15 Dimensional Outline ...
Страница 48: ...M3645P 48 Figure 6 5 M3645 M15 Line Reactor Dimensional Outline ...
Страница 50: ...M3645P 50 6 7 BLOCK DIAGRAM Figure 6 7 Typical Customer Application ...
Страница 53: ...User s Manual 53 NOTES ...
Страница 54: ...M3645P 54 ...
Страница 55: ......