background image

 

 Web: www.bonitron.com      ●       Tel: 615-244-2825      ●       Email: [email protected]

   

 

 
 
 
 

 

 

 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 

Model M3528M2 

Voltage Monitor Module 

 
 
 
 

Customer Reference Manual 

Содержание M3528M2

Страница 1: ...Web www bonitron com Tel 615 244 2825 Email info bonitron com Model M3528M2 Voltage Monitor Module Customer Reference Manual ...

Страница 2: ...design develop and manufacture the quality industrial electronic systems demanded in today s market A strong academic background supported by continuing education is complemented by many years of hands on field experience A clear advantage Bonitron has over many competitors is combined on site engineering labs and manufacturing facilities which allows the engineering team to have immediate access ...

Страница 3: ...Below is a sampling of Bonitron s current product offering WORLD CLASS PRODUCTS Undervoltage Solutions Overvoltage Solutions Uninterruptible Power for Drives DC Bus Ride Thru Voltage Regulators Chargers and Dischargers Energy Storage Braking Transistors Braking Resistors Transistor Resistor Combo Line Regeneration Dynamic Braking for Servo Drives Common Bus Solutions Portable Maintenance Solutions...

Страница 4: ...M3528M2 4 This page intentionally left blank ...

Страница 5: ...g 11 3 4 Wiring and Customer Connections 11 Figure 3 1 Typical Interconnection Diagram 12 3 4 1 Power Wiring 12 3 4 2 I O Wiring 12 Table 3 1 Wiring Specifications 13 4 OPERATION 15 4 1 Functional Description 15 4 2 Features 15 4 2 1 Connectors 15 4 2 2 Jumpers 16 Table 4 1 Setpoint Range Jumper Configurations 16 4 2 3 Potentiometers 17 Table 4 2 Setpoint Adjustment Sensitivity 17 Figure 4 1 Front...

Страница 6: ...M3528M2 6 This page intentionally left blank ...

Страница 7: ... Model M3528M2 Voltage Monitor Module It will provide the user with the necessary information to successfully install integrate and use the M3528M2 In the event of any conflict between this document and any publication and or documentation related to the DC storage system the latter shall have precedence 1 3 MANUAL VERSION AND CHANGE RECORD CE requirements for the M3528M2 are met in Rev 01 Wiring ...

Страница 8: ...tifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss CAUTION CAUTION Identifies information about practices or circumstances that can lead to property damage or economic loss Attentions help you identify a potential hazard avoid a hazard and recognize the consequences CAUTION CAUTION Heat or burn hazard Identifies a statemen...

Страница 9: ...534 and M3460 Ride Thru Systems Contact your distributor for more information 2 2 PART NUMBER BREAKDOWN BASE MODEL NUMBER The Base Model Number M3528 indicates that the unit is related to charger modules M specifies a monitor board and 2 specifies this particular unit There are no special options at this time 2 3 GENERAL SPECIFICATIONS Table 2 1 General Specifications Chart PARAMETER SPECIFICATION...

Страница 10: ...ED FOR EVALUATION AND OR REPAIR BY QUALIFIED TECHNICIANS BEFORE ATTEMPTING INSTALLATION OR REMOVAL OF THIS PRODUCT BE SURE TO REVIEW DOCUMENTATION OF ALL CONNECTED DEVISES FOR PERTINENT SAFETY PRECAUTIONS INSTALLATION AND OR REMOVAL OF THIS PRODUCT SHOULD ONLY BE ACCOMPLISHED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE OR EQUIVALENT REGULATIONS ANY QUESTIONS AS TO APPLIC...

Страница 11: ...t was received or the product is damaged in any way please contact the supplier from which the product was purchased 3 3 MOUNTING The unit is mounted with a standard DIN rail clip attached to the back of the enclosure Refer to Figure 6 1 to determine the correct mounting dimensions for your unit 3 4 WIRING AND CUSTOMER CONNECTIONS This section provides information about the field connection of the...

Страница 12: ... qualified electricians should perform and maintain the interconnection wiring of this product All wiring should be done in accordance with National Electrical Code or equivalent regulations 3 4 1 POWER WIRING The power connector supplies control power to the internal circuitry with power The system must be supplied with at least 30 mA at 24VDC to guarantee correct functioning 3 4 2 I O WIRING The...

Страница 13: ... 2 2 lb in TB3 2 Overvoltage Latch Reset Input 24VDC common to TB3 1 18 16 2 2 lb in TB3 3 Undervoltage Latch Reset Input 24VDC to TB3 4 18 16 2 2 lb in TB3 4 Undervoltage Latch Reset Input 24VDC common to TB3 3 18 16 2 2 lb in TB4 1 Overvoltage Output NC 350VDC 120 mA max 18 16 2 2 lb in TB4 2 Overvoltage Output COM 350VDC 120 mA max 18 16 2 2 lb in TB4 3 Overvoltage Output NO 350VDC 120 mA max 1...

Страница 14: ...M3528M2 14 This page intentionally left blank ...

Страница 15: ...TB2 1 2 POWER The power connector accepts 24VDC to supply power to the voltage monitor board 4 2 1 3 TB3 1 2 OVERVOLTAGE LATCH RESET The isolated latch reset connector accepts a 24VDC overvoltage latch reset signal When a latch reset signal is received any latch on the overvoltage channel is cleared 4 2 1 4 TB3 3 4 UNDERVOLTAGE LATCH RESET The isolated latch reset connector accepts a 24VDC undervo...

Страница 16: ... these jumpers may be seen in Table 4 1 Setpoint Range Jumper Configurations Please ensure that the voltages connected to the system remain within the range determined by the range jumper settings or correct system operation is not guaranteed and damage to the monitor board may result Table 4 1 Setpoint Range Jumper Configurations MONITOR RANGE 850V 500V 100 850V ON 50 500V OFF ON 10 100V OFF OFF ...

Страница 17: ...t resets at a different input level This hysteresis prevents rapid switching between output states in cases that the input voltage is very close to a set point The hysteresis range for each channel is controlled by adjusting a potentiometer The hysteresis range can be set to between 3 and 100 of the maximum setpoint range as determined by the jumper settings in Table 4 1 Turn the hysteresis potent...

Страница 18: ...M3528M2 18 Figure 4 1 Front View Dwg 080333 Rev 20080812 ...

Страница 19: ... RETURNS TO SET RANGE Ensure that the output latch jumpers are open Reduce the hysteresis value by turning the hysteresis potentiometers counter clockwise OUTPUT NEVER SWITCHES Ensure that the ranging jumpers are correctly set for the voltage being tested Turn the appropriate setpoint potentiometer counterclockwise a full twenty turns and then clockwise a full twenty turns until the signal switche...

Страница 20: ...M3528M2 20 This page intentionally left blank ...

Страница 21: ... 408 420 432 480 Battery bank full charge voltage 243 270 459 473 486 540 M3528M2 Set Points Over Voltage trip level 5 over full charge 255 284 470 484 498 553 Over Voltage reset level full charge 243 270 459 473 486 540 Under Voltage trip level 84 of nominal 180 200 340 350 360 400 Under Voltage reset level nominal voltage 216 240 408 420 432 480 6 2 DIMENSIONS AND MECHANICAL DRAWINGS Figure 6 1 ...

Страница 22: ...M3528M2 22 NOTES ...

Страница 23: ......

Страница 24: ...D_M3528M2_CMAN_VALL_01b 04 04 2014 521 Fairground Court Nashville TN 37211 USA Tel 615 244 2825 Fax 615 244 2833 Web www bonitron com Email info bonitron com ...