EM-RES-03
35
10/07
10/07 EM-RES-03
35
5.11.3
Timeout monitoring process data channel
Each frequency inverter monitors its received data for whether they are updated
within a defined time window.
The monitoring is done onto the SYNC telegram and the RxPDO channels.
Monitoring SYNC / RxPDO‘s
Parameter
Setting
No.
Description
Min. Max. Fact.
sett.
939 SYNC Timeout
0 ms
60000 ms
0 ms
941 RxPDO1 Timeout
0 ms
60000 ms
0 ms
942 RxPDO2 Timeout
0 ms
60000 ms
0 ms
945 RxPDO3 Timeout
0 ms
60000 ms
0 ms
Setting "0" means no timeout monitoring.
Attention:
There is only monitoring for the SYNC telegram if at least one RxPDO or
one TxPDO channel is defined as SYNC controlled.
If a timeout period is exceeded, the frequency inverter switches to failure mode and
reports one of the faults:
F2200
System bus Timeout SYNC
F2201
System bus Timeout RxPDO1
F2202
System bus Timeout RxPDO2
F2203
System bus Timeout RxPDO3