Accessing data via PROFINET
22
Operating manual for PROFINET fieldbus | DOC01725815-0003 | 2016-12 | V2.04 EN
4.1.2
Structure of DGM status word
The meanings of the individual bits of the DGM status word are described in the following table.
Bit
Value
Meaning
Description
0
1
Ready for engagement
Grid voltage present, no fault
0
Not ready for engagement
1
1
Ready for operation
No fault / HW enable set
0
Not ready for operation
2
1
Operation
Motor is energised
0
Operation blocked
3
1
Error active
A fault is present
0
Free from faults
4
1
No OFF 2
On 2 off / STW bit 1 set ³(logic can be inverted
with parameter 6.066.)
0
Electr. stop active (OFF 2)
5
1
No OFF 3
On 3 off / STW bit 2 set ³(logic can be inverted
with parameter 6.066)
0
Rapid stop active (OFF 3)
6
1
Engagement inhibit active
1
PWM blocked
0
No engagement inhibit
1
PWM enabled
7
1
Warning active
2
A warning is present
0
No warning
8
1
Nominal/actual value
deviation in tolerance range
Actual value within a tolerance band
Parameter 6.070 / 6.071
0
Nominal/actual value
deviation outside tolerance
range
9
1
Control from AG
DGM is parameterized for activation via
fieldbus
0
No control from AG
10
1
Target frequency reached
Actual frequency > = reference value
(Parameter 6.072)
0
Target frequency fallen below
Actual frequency < reference value
Continues next page