Operating manual for DGM Modular | DOC02389740-0006 | 2021-07 | V1.70 EN
69
5.4 Performance parameters
5.4.1
Drive type
33.010
Drive type
Unit: integer
Relationship to
parameter:
Transfer status:
1
min.:
0
Own value (to be entered!)
max.:
299
def.:
20
Drive type
V/f
ASM
PMSM
SRM
x
x
x
x
This can be used to select the motor type and type of control.
10 = ASM V/f
20 = ASM open-loop (motor identification needed)
100 = PMSM standard mode (motor identification needed)
110 = PMSM efficiency mode*
210 = RSM efficiency mode*
* For special motors
5.4.2
Motor data
33.020
R optimisation
Unit: %
Relationship to
parameter:
Transfer status:
1
min:
0
Own value (to be
entered!)
max:
200
def.:
100
Drive type
V/f
ASM
PMSM
SRM
x
If necessary, this parameter can be used to optimise the start-up behaviour.
33.031
Motor current
Unit: A
Relationship to
parameter:
5.070
Transfer status:
1
min.:
0
Own value (to be entered!)
max.:
150
def.:
0
Drive type
V/f
ASM
PMSM
SRM
x
x
x
x
This is used to set the nominal motor current I
M,N
for either the star or delta connection.
33.032
Motor rating
Unit: W
Relationship to
parameter:
Transfer status:
1
min.:
0
Own value (to be entered!)
max.:
55000
def.:
0
Drive type
V/f
ASM
PMSM
SRM
x
x
x
A performance value P
M,N
has to be set here that corresponds to the nominal motor rating.
Содержание DGM MPM
Страница 1: ...Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN 1...
Страница 2: ...2 Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN...
Страница 3: ...Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN 3...
Страница 98: ......
Страница 102: ......
Страница 104: ......
Страница 105: ...Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN 101...
Страница 106: ......
Страница 107: ...Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN 103...