Operating instructions Typ 2200

25 / 32

Betriebsanleitung Typ 2200

4.5

Controllers of type 6.62

Inputs 6.62
"Position reached" limit switch
Pressure switch "DP reached, backflushing filter" 

 75 %

Pressure switch "DP too high, backflushing filter" 

 100 % 

Outputs 6.62
Flushing valve
Chamber valve supplied with pulse

Potential-free contacts and messages 6.62

Potential-free  contacts  and  messages  6.62  Alarm  DP  (flushing  frequency        

monitoring)

Functional description 6.62
See the operating instructions for the filter's function.

Flushing is triggered by:

Special attributes

When  flushing  is  triggered  by  switching  on  the  power  and  an  open  limit            

switch, a flushing cycle starts directly with the flushing valve.

If  the  controller  is  in  parameterisation  mode,  flushing  cannot  be  triggered          

manually.

If the "Controller type" parameter is changed, the functions are re-started.

1) "Control voltage monitoring" alarm

Output A1, A2, A3

2) Group fault:  

"Max differential pressure reached" alarm

Output A4, A5, A6

1) "Control voltage monitoring" alarm

Output A1, A2, A3

2) Group fault:  

"Maximum differential pressure reached" alarm

Output A4, A5, A6

3) "Backflushing triggered by DP" alarm

Output A7, A8, A9

1)  Switching on the power supply
2) Key F
3) The forced flushing time elapsing
4) Pressure switch "DP reached, backflushing filter"

Содержание 2200

Страница 1: ...ructions Electronic controller Type 2200 Siemensstraße 10 14 50170 Kerpen Germany www bollfilter de Date Version Language Order no Item no 05 2015 008 en NOTE Print document on both sides Translation of the original operating instructions ...

Страница 2: ...2 32 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 ...

Страница 3: ...flushes 10 3 1 7 Multiple flushing 10 3 1 8 DP alarm flushing frequency monitoring 11 3 2 Display for Operation mode 11 3 3 Text messages 11 3 3 1 Text display after switching on 11 3 3 2 Text display in Operation mode 12 3 3 3 Alarm messages 13 3 4 Setting and operation 13 3 4 1 Setting level Viewing and selecting parameters 13 3 4 2 Setting level Changing and saving parameters 13 3 4 3 Return to...

Страница 4: ...g Typ 2200 4 2 Controllers of types 6 21 6 22 6 23 6 24 20 4 3 Controllers of type 6 60 21 4 4 Controllers of type 6 61 23 4 5 Controllers of type 6 62 25 4 6 Controllers of type 6 64 26 4 7 Controllers of type 6 72 28 5 Appendix 31 5 1 Setting values 31 ...

Страница 5: ... attention to the following points The controller must be installed by qualified specialist staff only as defined by the guidelines IEC 364 DIN VDE 0105 for electrical equipment The laws guidelines directives and regulations for the installation of electrical equipment which are valid at the location for installation must be adhered to Settings on devices with protection class IP00 without covers ...

Страница 6: ...6 32 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 ...

Страница 7: ... U V W direct to motor contactor K1 2 4 6 2 1 3 Power supply 2 1 4 Fuse protection Primary voltages 0 220 V 380 V 400 V 440 V 500 V 550 V Secondary voltages 0 V AC 230 V AC Valve voltage 230 V AC 0 V AC 115 V AC Valve voltage 115 V AC 0 V DC 24 V DC Valve voltage 24 V DC 0 V AC 20 V AC Control circuit board supply voltage Fuses in the control cabinet F1 to F3 each 1 A Fuses on the control circuit ...

Страница 8: ... can be found in the respective circuit diagrams 2 2 3 Potential free relay outputs NOTE The connections and designations depend on the type of filter and can be found in the respective circuit diagrams 2 3 Circuit diagrams The circuit diagrams for the controller are contained in the appendix of these operating and installation instructions Outputs VE1 VN1 to VE3 VN3 Terminals 8 13 Outputs A1 A15 ...

Страница 9: ...ence Fig 3 1 Electronic controller type 2200 Fig 3 2 Display and operating elements 1 Fastening 2 Display and operating elements 3 Housing 4 Master switch 5 Connection 1 Display screen for text display 2 lines of 16 characters 2 Alarm LED red 3 Service LED yellow 4 Operation LED green 5 Keypad 1 2 3 4 5 1 2 3 4 5 ...

Страница 10: ...h off immediately Once the fault has been remedied the user has to acknowledge the alarm message by pressing the Q key 3 1 4 Differential pressure too high flushing oil treatment cartridge alarm The signal transmitter is a pressure switch contact which is connected to the Differential pressure indicator DP too high flushing oil treatment optocoupler input If the message is active for a longer peri...

Страница 11: ...g on After a short delay the parameterised controller type is displayed in the second line of the display Boll Kirch Company name xxxxxxxxxx Programme number 6 18 6 19 6 44 Controller type 0 6 21 6 22 6 23 6 24 Controller type 1 6 60 Controller type 2 6 60 Alarm DP Controller type 3 6 60 07 6 72 07 Controller type 4 6 60 07 6 72 07 AL DP Controller type 5 6 61 Controller type 6 6 61 Alarm DP Contr...

Страница 12: ...sage appears on the display screen The number of flushing cycles is saved and backed up in the event of a mains failure forced fl 00 01 Remaining time till forced flushing is triggered 00 h 01 min C F Q Reference to keys Mains flushing When flushing is triggered by Power supply on Manual flushing When flushing is triggered by the F key forced flushing When flushing is triggered by time controlled ...

Страница 13: ...ately 3 seconds The first display line shows the parameter and the second line shows the parameter value All parameters can now be displayed by repeatedly pressing the key or 3 4 2 Setting level Changing and saving parameters In order to access the setting level Changing and saving parameters press the middle key until the green Operation LED flashes approximately 3 seconds The parameter can now b...

Страница 14: ... 17 Factory setting Initial value 0 Text display line 1 P0 filter type Text display line 2 6 18 6 19 6 44 Adjustable in steps of one Range 1 99 x Factory setting Initial value 1 Text display line 1 P1 multiple fl Text display line 2 XXX chambers Adjustable in steps of one hour Range 0 59 h Factory setting Initial setting 2 h Text display line 1 P2 forced flush Text display line 2 XXX hours Adjusta...

Страница 15: ...isible with filter type P0 4 5 8 9 14 15 Adjustable in steps of one second Range 5 100 s Factory setting Initial value 20 s Text display line 1 P4 flushing time Text display line 2 XXX seconds Adjustable in steps of 10 seconds Range 10 600 s Factory setting Initial value 180 s Text display line 1 P5 Filling time Text display line 2 XXX seconds Adjustable in steps of one second Range 5 100 s Factor...

Страница 16: ...ult NOTE This parameter is only visible with filter type P0 0 6 7 8 9 12 13 14 15 Adjustable in steps of 10 seconds Range 10 600 s Factory setting Initial value 30 s Text display line 1 P7 Cartridge al Text display line 2 XXX seconds Setting Off On Factory setting Initial setting On Text display line 1 P8 DP alarm Text display line 2 Off or Text display line 2 On Adjustable in steps of 0 01 A Rang...

Страница 17: ...he parameter is not required if the setting is P0 1 NOTE For filter type 6 21 6 22 the backflushing time must generally be set to ND 50 3 3 5 12 P11 Language You can select from German English French and Spanish Adjustable in steps of one Range 0 to 2 Factory setting Initial setting ND 32 1 s Text display line 1 P10 flush time Text display line 2 ND XX XX sec Setting D German ES Spanish F French G...

Страница 18: ...vided for authorised persons only 3 5 14 P14 Pressure compensation time NOTE This parameter is only visible with filter type P0 12 13 14 15 Adjustable in steps of one Range 0 to 250 Factory setting Initial value 0 Text display line 1 P12 Testcode Text display line 2 XXX Adjustable in steps of one second Range 0 to 99 s Factory setting Initial value 10 s Text display line 1 P14 PET Text display lin...

Страница 19: ...ing is triggered by Special attributes All alarms are displayed and signalled and saved via potential free contacts If the controller is in parameterisation mode flushing cannot be triggered manually If the Controller type parameter is changed the functions are re started 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output A4 A5 A6 Maximum differential pressure ...

Страница 20: ...al description 6 21 6 22 6 23 and 6 24 See the operating instructions for the filter s function Flushing is triggered by Special attributes All alarms are displayed and signalled and saved via potential free contacts If the controller is in parameterisation mode flushing cannot be triggered manually If the Controller type parameter is changed the functions are re started 1 Control voltage monitori...

Страница 21: ...60 07 and 6 60 07 Alarm DP After blowing valve Potential free contacts and messages 6 60 Potential free contacts and messages 6 60 Alarm DP Potential free contacts and messages 6 60 07 1 Control voltage monitoring alarm Output A1 A2 A3 2 Group fault Maximum differential pressure reached alarm Output A4 A5 A6 1 Control voltage monitoring alarm Output A1 A2 A3 2 Group fault Maximum differential pres...

Страница 22: ...ushing frequency alarm Special attributes All alarms are displayed and signalled and saved via potential free contacts If the controller is in parameterisation mode flushing cannot be triggered manually If the Controller type parameter is changed the functions are re started 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output A4 A5 A6 Maximum differential pressu...

Страница 23: ...alve Potential free contacts and messages 6 61 Potential free contacts and messages 6 61 Alarm DP Potential free contacts and messages 6 61 07 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output A4 A5 A6 Maximum differential pressure reached alarm and Motor fault alarm 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output A4 A5 ...

Страница 24: ... the flushing valve If the controller is in parameterisation mode flushing cannot be triggered manually If the Controller type parameter is changed the functions are re started 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output A4 A5 A6 Maximum differential pressure reached alarm Motor fault alarm and Cartridge alarm DP alarm flushing oil treatment 3 Backflushi...

Страница 25: ...Special attributes When flushing is triggered by switching on the power and an open limit switch a flushing cycle starts directly with the flushing valve If the controller is in parameterisation mode flushing cannot be triggered manually If the Controller type parameter is changed the functions are re started 1 Control voltage monitoring alarm Output A1 A2 A3 2 Group fault Max differential pressur...

Страница 26: ...wing valve Potential free contacts and messages 6 64 Potential free contacts and messages 6 64 Alarm DP Potential free contacts and messages 6 64 07 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output A4 A5 A6 Maximum differential pressure reached alarm and Motor fault alarm 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output ...

Страница 27: ...piry of the pressure compensation time If the controller is in parameterisation mode flushing cannot be triggered manually If the Controller type parameter is changed the functions are re started 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output A4 A5 A6 Maximum differential pressure reached alarm Motor fault alarm and Cartridge alarm DP alarm flushing oil tre...

Страница 28: ...72 07 and 6 72 07 Alarm DP After blowing valve Potential free contacts and messages 6 72 Potential free contacts and messages 6 72 Alarm DP Potential free contacts and messages 6 72 07 1 Control voltage monitoring alarm Output A1 A2 A3 2 Group fault Maximum differential pressure reached alarm Output A4 A5 A6 1 Control voltage monitoring alarm Output A1 A2 A3 2 Group fault Maximum differential pres...

Страница 29: ...ushing frequency alarm Special attributes All alarms are displayed and signalled and saved via potential free contacts If the controller is in parameterisation mode flushing cannot be triggered manually If the Controller type parameter is changed the functions are re started 1 Control voltage monitoring alarm Output A1 A2 A3 2 Collective fault comprising Output A4 A5 A6 Maximum differential pressu...

Страница 30: ...30 32 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 ...

Страница 31: ...Operating instructions Typ 2200 31 32 Betriebsanleitung Typ 2200 5 Appendix 5 1 Setting values ...

Страница 32: ...32 32 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 ...

Отзывы: