Section 4-
1-
No AC Output (Inverter series)
This could be a loose wire from the inverter to the receptacles. Check to see if the red and black wires are securely
plugged in and the wires are securely attached to the receptacles.
Check 3pin blue connector. the reading should be 0.8~1ohm. The voltage should be 160~220V.
2
- No DC out put
Check the Protector switch, Keep the "ON", If ok, please check the DC wire connector.
Section5-
1.High Speed, Ignition be disconnected, ECON switch failure.
Open the control panel. Check ECON switch connector whether or not ok.
1-White wire
2-Green wire
3-Yellow wire
In the control panel. Check 2 pin connector (Red wire) .The reading should be 0.8~1.0 ohm. the rated voltage
170V~230V.
Check feedback signal 4 pin connector (From generator fan-out).
1-2 White wire 0.2~0.3 ohm rated voltage 12~16V(AC)
3~4 Yellow wire 0.4~0.45 ohm rated voltage 85~145V(AC)
If the reading accord with above data. Please replace the controller.