![bolid S2000M Скачать руководство пользователя страница 3](http://html.mh-extra.com/html/bolid/s2000m/s2000m_installation-manual_2785117003.webp)
http://bolid.ru/
3
4
CONNECTING PANEL
The S2000M's connectivity is described in Table 1. The conductors of the cable for
connections shall be not less than 0.2 mm
2
in cross section and no more than 1.5 mm
2
.
Table 1: S2000M Connectivity
Legend
Descriptions
0V
- power 10.2 … 28.4 V (primary supply)
+U1
+ power 10.2 … 28.4 V (primary supply)
0V
- power 10.2 … 28.4 V (backup supply)
+U2
+ power 10.2 … 28.4 V (backup supply)
A
RS-485 input/output
B
RS-485 inverse input/output
TxD
RS-232 data output
RxD
RS-232 input:
Printer ready signal (when connecting a printer) or data received (for other
operating modes of the RS-232 interface)
GND
RS-232 common circuit
Figure 3.
External Connections
4.1 Connecting RS-485 Lines
4.1.1 When installing RS485 line, it is recommended using twisted pair cable. If RS485 line
is 100 meters or longer, only a twisted pair must be used.
4.1.2 The Bus topology is recommended for the RS485 line (see Figure 4). If needed, the
RS485 trunk can be branched with short branches (no longer than 100 meters). Longer
branches shall be made using S2000-PI interface converter (see Fig. 6)
4.1.3 The maximum length of RS485 line is 3,000 meters, if cable of 0.5 mm
2
conductors is
used. If cable of 0.2mm
2
conductors is used, the recommended RS485 line length is no
longer than 1,200 meters. The RS485 line can be extended using the S2000-PI interface
converter as shown in Figure 5.
4.1.4 To connect the panel to RS485 interface, please connect A and B lines of RS485
interface to A and B terminals on terminal strip
XT1
+U1
0V
+U2
0V
B
A
TxD
GND
RxD
Primary power supply
RS-485
RS-232
0 V
+U1
+U2
0 V
A
B
TxD
RxD
GND
Backup power supply