background image

 

1

ADDRESSABLE EXECUTIVE MODULE 

S2000-SP4/220 Ver 1.04 

INSTRUCTION MANUAL 

1

 

TECHNICAL DATA 

1.1

 

General 

1.1.1

 

This Instruction Manual describes S2000-SP4/220 Addressable Executive Module along 

with its operation algorithms and characteristics. 

1.1.2

 

The  module  is  used  as  part  of  a  multipart  executive  device  in  fire  and  intrusion  alarm 

systems  under  control  of  an  S2000-KDL  ver.2.01+  or  S2000-KDL-2I  ver.1.00+  controller  and  an 
S2000M console. 

1.1.3

 

Meeting requirements for sound and light indication of control and indicating equipment 

is provided together with the S2000-KDL and S2000M. 

1.1.4

 

The  module  is  designed  to  monitor  and  control  fire  dampers,  smoke  control  dampers, 

deluge valves, and other executive devices powered by mains power 220 V. 

1.1.5

 

The module is to be attached at a suitable place (on a wall, above a suspended ceiling, or 

on  another  constructions  near  the  connected  executive  device)  protected  against  atmospheric 
fallouts, mechanical damage, and unauthorized access. The module is designed for round-the-clock 
operation. 

1.1.6

 

The  module must not be used in aggressive  medium or dust condition, or in explosion-

hazardous premises. 

1.1

 

Specifications 

Table 1. Specifications 

1)

 

Input Voltage 

 

Communication Part 

 

8 V to 12 V via the polling loop 

Executive Part 

 

An external power supply, 220 V ac 

2)

 

Insulating Voltage of the Polling Loop 

and Executive Part 

 

Up to 500 V 

3)

 

Consumed Current: 

 

Communication Part 

 

1.5 m

А

 max 

Executive Part 

 

50 m

А

 max(without regard to output’s current) 

4)

 

Outputs 

 

5)

 

Max Switching Current per an Output 

 

А

 

6)

 

Switching Voltage 

 

220 V 

7)

 

Circuit Control Current 

 

0.5 m

А

 max 

8)

 

Monitored Limit Switches 

 

9)

 

Pre-Operation Time 

 

15 s max 

10)

 

Operating Temperatures 

 

Minus 30

°

C to +55

°

С

 

11)

 

Humidity  

 

93 % at +40

°

С

 

12)

 

Overall Dimensions 

 

156 mm 

×

 107 mm 

×

 39 mm 

13)

 

Weight 

 

0.2 kg max 

14)

 

Ingress Protection Rating  

 

IP20 

 

IP30, if wall mounted 

Содержание S2000-SP4/220

Страница 1: ...ended ceiling or on another constructions near the connected executive device protected against atmospheric fallouts mechanical damage and unauthorized access The module is designed for round the clock operation 1 1 6 The module must not be used in aggressive medium or dust condition or in explosion hazardous premises 1 1 Specifications Table 1 Specifications 1 Input Voltage Communication Part 8 V...

Страница 2: ...the output relative to the N terminal of the power input Table 3 States of an Output Circuit Condition Output State L R Terminal N R Terminal Norm On Input Voltage Value 0 3 V to 0 9 V Off 0 35 V to 4 5 V 0 3 V to 0 6 V Open Failure On Input Voltage Value 0 V to 0 3 V Off 4 5 V to 5 V 0 V to 0 3 V Short Failure On Input Voltage Value Input Voltage Value Off 0 3 V to 0 6 V 0 3 V to 0 6 V Note If an...

Страница 3: ...rent position of the damper s blades open closed 2 2 3 A limit switch circuit can be in one of the four states which are defined by the circuit resistance Table 5 shows the ranges of resistance values for relative states of the limit switch circuits 2 3 TEST Button 2 3 1 The module provides connecting an external button TEST 2 3 2 The TEST button is designed to test damper operation conditions man...

Страница 4: ...le MUST be performed by qualified engineers 3 2 Preparation for Using 3 2 1 If necessary change the module s addresses within the polling loop of the connected S2000 KDL The addresses of the module must not be the same as addresses of any devices connected to the same polling loop 3 2 2 If you are going to use the module with a single power supply the power supply should be connected to both power...

Страница 5: ...r to the S2000 SP4 220 Manufacturer Article How to Connect Belimo BLF 230 Directly to the required output the unused output is shunted by a 47 kOhm 2 W resistance Belimo BE 230 Directly without additional elements Belimo BLE 230 Directly without additional elements ...

Страница 6: ...Address command from the console or PC specifying the old address the first of the five old addresses and the new address the first of the five new addresses of the module In such case the console or PC will display events about disconnecting the devices with the old addresses and finding the devices with the newly given addresses 3 4 Using The module operates under the connected S2000 KDL control...

Страница 7: ...vert the current damper state For example if the damper is in the operating state pushing the TEST button will run the mechanism of switching the damper to the safety state 4 MAINTENANCE Please inspect the module annually by doing the following 1 Check the S2000 SP4 220 visually for contaminations and mechanical damage 2 Test the S2000 SP4 220 operability as said above 3 Verify the S2000 SP4 220 f...

Отзывы: