5  TESTING 

5.1 Testing the module shall be carried out by personnel qualified for the Electrical Safety of 
Level II or higher. 

5.2 Do  shut  off  power  from  the  polling  loop  controller  while  connecting  and  disconnecting 
external circuits. 

5.3 Performance Testing 

5.3.1 Apply power to the polling loop controller. 

5.3.2 By  means  of  the  network  controller  arm  the  detector  with  the  number  assigned  with 
MC1 in the module. 

5.3.3 Simulate an alarm response of the detector connected to MC1. The module LED shall 
start flashing doubly every four seconds. The network controller shall display Intrusion Alarm 
or Fire Alarm for the address assigned to the module’s MC1. 

5.3.4  Place the detector into the normal state. The module LED shall start flashing once eve-
ry four seconds. By means of the network controller issue a command to reset alarm from the 
detector related to MC1. When one monitored circuit is being tested the other circuit shall be 
in norm. 

5.3.5 Perform actions 5.3.2 - 5.3.4 for the monitored circuit MC2. 

5.3.6 If  no  Intrusion / Fire Alarm  message  has  come  on  the  network  controller  then  the 
module is considered as defective and should be replaced. 

5.3.7 By  means  of  the  network  controller  request  for  ADC  values  representing  monitored 
circuit states (see User’s Manual). 

6  GETTING STARTED 

In  order  the  S2000-AR2  Rev.02  to  operate  under  a  polling  loop  controller  in  an  Orion  ISS,  it 
should  be  assigned  to  a  polling  loop  address  and  the  relevant  settings  should  be  carried  out 
(see User’s Manual).

 

Содержание S2000-AR2

Страница 1: ...d out by personnel qualified for the Electrical Safety of Level II or higher 2 INSTALLATION 2 1 The module is to be installed on a wall above a suspended ceiling or on another structure of the protected premises at a place protected against atmospheric precipitations mechanical damages and unauthorized access 2 2 The module should be mounted in line with Regulatory Document РД 78 145 93 Fire and I...

Страница 2: ...erall and Mounting Dimensions of S2000 AR2 Rev 02 Figure 2 Opening S2000 AR2 Rev 02 Enclosure Figure 3 Closing S2000 AR2 Rev 02 Enclosure 1 Put one long end of the cover on the enclosure base 2 Snap on the other end of the cover ...

Страница 3: ...ed 100 Ohm while the leakage resistance shall be at least 50 kOhm 4 2 3 If a monitored circuit is not in use connect a 10 kOhm termination resistor to its contacts 4 3 Close the module enclosure as shown in Figure 3 КЦ1 ДПЛС КЦ2 AD Addressable Device MC Monitored Circuit D1 A normally closed fire detector D2 A normally open fire detector D3 A normally open intrusion detector D4 A normally closed i...

Страница 4: ...o the module s MC1 5 3 4 Place the detector into the normal state The module LED shall start flashing once eve ry four seconds By means of the network controller issue a command to reset alarm from the detector related to MC1 When one monitored circuit is being tested the other circuit shall be in norm 5 3 5 Perform actions 5 3 2 5 3 4 for the monitored circuit MC2 5 3 6 If no Intrusion Fire Alarm...

Отзывы: