English
3/4
BS125-175
6 Maintenance
a) Th
e machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the mainte-
nance performed;
b) when requesting assistance or spare parts, identify the machine
(model and serial number) by reading the data plate located on the
unit.
6.1 General instructions
!
Before any maintenance, make sure:
• the pneumatic circuit is no longer pressurized;
• the dryer is disconnected from the main power supply
.
Y
Always use the Manufacturer’s original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunction-
ing
Y
In case of refrigerant leakage, contact qualifi ed and authorized per-
sonnel.
Y
Th
e Schrader valve must only be used in case of machine malfunc-
tion: otherwise any damage caused by incorrect refrigerant charging will
not be covered by the warranty.
6.2 Refrigerant.
Charging: any damage caused by incorrect refrigerant replacement car-
ried out by unauthorized personnel will not be covered by the warranty.
Z
Y
At normal temperature and pressure, the R134a refrigerant is a
colourless gas classifi ed in SAFETY GROUP A1 - EN378 (group 2 fl uid
according to Directive PED 2014/68/EU)
GWP (Global Warming Potential) = 1430.
!
In case of refrigerant leakage, ventilate the room.
6.3 Preventive Maintenance Programme
To guarantee lasting maximum dryer effi
ciency and reliability
Maintenance
Activity Description
Maintenance Interval
(standard operating conditions
)
Activity
Check
Service
Da
ily
W
eek
ly
4 M
on
ths
12 M
on
ths
Check POWER ON indicator is lit.
Check control panel indicators.
Check condensate drain.
Clean condenser fi ns.
Check electrical absorption.
Depressurize the dryer. Complete
drain maintenance.
Depressurize the dryer. Replace pre-
and post-fi lter elements.
Th
e following are available (see par. 8.4):
a) compressor kits;
b) fan kits;
c) automatic expansion valve kits;
d) individual spare parts.
6.4 Dismantling
Th
e refrigerant and the lubricating oil contained in the circuit must be
recovered in conformity with current local environmental regulations.
%
Recycling Disposal
Z
structural work
steel/epoxy-polyester resins
exchanger
aluminium
pipes
aluminium/copper
drain
polyamide
exchanger insulation
EPS (sintered polystyrene)
pipe insulation
synthetic rubber
compressor
steel/copper/aluminium/oil
condenser
steel/copper/aluminium
refrigerant
R134a
valves
brass
electrical cables
copper/PVC
Содержание BS125-175
Страница 2: ......
Страница 19: ... Appendix 1 BS125 175 Appendice Anhang Appendix Anexo ...
Страница 25: ... 8 6 Dimensional drawing 7 BS125 175 i n c h e s mm ...
Страница 26: ... 8 7 Refrigerant circuit 8 BS125 175 BS125 BS150 175 ...
Страница 27: ... 8 8 Wiring diagram BS125 9 BS125 175 230 Vac ...
Страница 28: ... 8 8 Wiring diagram BS150 10 BS125 175 230 Vac ...
Страница 29: ... Wiring diagram BS175 11 BS125 175 ...
Страница 30: ......
Страница 31: ......