READ AND FOLLOW ALL SAFETY INSTRUCTIONS

! IMPORTANT SAFEGUARDS !

WHEN USING ELECTRICAL EQUIPMENT, BASIC

SAFETY PRECAUTIONS SHOULD ALWAYS BE 

FOLLOWED, INCLUDING THE FOLLOWING:

SAVE THESE INSTRUCTIONS

© Philips Emergency Lighting

236 Mt. Pleasant Rd. • Collierville, TN 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.philips.com/bodine

70100047

BRANCH CIRCUIT 

TRANSFER SWITCH/LIGHTING CONTROL DEVICE

Installation Instructions

 

1.  This product is for use with generator-supplied (or central inverter system-supplied) lighting loads. Make sure  all 

     connections are in accordance with the National Electrical Code and any local regulations.
  2.  To reduce the risk of electric shock, disconnect all power sources before servicing.
  3.  This product is for field installation.
  4.  This product is for use in indoor or damp locations where the ambient temperature is -20ºC minimum, +55ºC  
   maximum.
  5.  This product is UL Listed as either a Branch Circuit Emergency Lighting Transfer Switch (BCELTS) under UL 1008  
    or a Switch Bypass under UL 924. Use the proper wiring diagram in the appropriate section of these instructions.
  6.  An unswitched, normal AC power source (120 through 277 VAC, 50/60 Hz) and a direct, separate connection to a  
    generator-supplied or central inverter system-supplied emergency panel are required.
  7.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
  8.  Do not use this product for other than intended use.
  9.  Servicing should be performed by qualified service personnel.

GTD20A

CAUTION:  

THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT. TO REDUCE  

     

THE RISK OF ELECTRIC SHOCK, DISCONNECT ALL POWER SOURCES BEFORE  

     

INSTALLING OR SERVICING THIS UNIT.

NOTE:

 BEFORE INSTALLING THE CONTROL DEVICE, MAKE SURE THAT THE NECESSARY BRANCH  

CIRCUIT WIRING IS AVAILABLE. AN UNSWITCHED SOURCE OF NORMAL POWER IS REQUIRED. A SEPARATE  
CONNECTION TO A GENERATOR-SUPPLIED (OR CENTRAL INVERTER SYSTEM-SUPPLIED) CIRCUIT MUST ALSO
BE PROVIDED.

SERVICE BY QUALIFIED PERSONNEL ONLY

06/19/18

UL 1008-BCELTS                  UL 924-Switch Bypass

Содержание GTD20A

Страница 1: ...ch Circuit Emergency Lighting Transfer Switch BCELTS under UL 1008 or a Switch Bypass under UL 924 Use the proper wiring diagram in the appropriate section of these instructions 6 An unswitched normal AC power source 120 through 277 VAC 50 60 Hz and a direct separate connection to a generator supplied or central inverter system supplied emergency panel are required 7 The use of accessory equipment...

Страница 2: ...cation using appropriate hardware not supplied See Illustration 1 for typical installation DO NOT MOUNT WITH LID FACING DOWN See Illustration 2 ILLUSTRATION 1 WALL MOUNTING STEP 2 INSTALLING THE GTD20A Disconnect AC power from all supply circuits Remove GTD20A lid and install necessary conduit and wiring not supplied to the GTD20A Refer to the illustrations on the following pages for proper wiring...

Страница 3: ...Y LOCAL SWITCHING MEANS LIGHTING LOAD UP TO 20 A 1 2 3 4 5 6 7 HOT NEUTRAL NORMAL CKT BKR PANEL HOT NEUTRAL HOT NEUTRAL WIRE GAUGES FOR ALL LEADS TERMINATING AT T2 SHOULD BE 18 AWG JUMPER CONNECTIONS ON T1 AND T2 ARE CONTRACTOR INSTALLED 4 5 6 7 1 2 3 1 2 3 4 5 6 7 DIMMING RACK GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 EMERGENCY CKT BKR PANEL LIGHTING LOAD UP TO 20 A HOT NEUTRAL NORMAL...

Страница 4: ...G DRIVER PURPLE LEADS TO DIMMING DRIVER GRAY LEADS PURPLE GRAY 1 2 3 4 5 6 7 GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 EMERGENCY CKT BKR PANEL LIGHTING LOAD UP TO 20 A HOT NEUTRAL NORMAL CKT BKR PANEL HOT NEUTRAL HOT NEUTRAL WIRE GAUGES FORALLLEADS TERMINATINGATT2 SHOULD BE 18AWG JUMPER CONNECTIONS ON T1AND T2ARE CONTRACTOR INSTALLED 0 10 VDC DIMMER BLK BLK WHT IF PROVIDED NOTE Wire ga...

Страница 5: ...WITCHING MEANS GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 HOT HOT NEUTRAL NEUTRAL WIRE GAUGES FOR ALL LEADS TERMINATING AT T2 SHOULD BE 18 AWG JUMPER CONNECTIONS ON T1 AND T2 ARE CONTRACTOR INSTALLED 4 5 6 7 1 2 3 NORMAL CKT BKR PANEL DIMMED HOT TO DIMMING DRIVERS SWITCHED HOT TO DIMMING DRIVERS NEUTRAL TO DIMMING DRIVERS EMERGENCY CKT BKR PANEL 1 2 3 4 5 6 7 DIMMING CONTROL GTD20A ELEC...

Страница 6: ... LED should extinguish and the controlled lighting load should illuminate regardless of the local switch position provided emergency power is available check red LED During a quick test using a GTD20A with a dimming system the lighting load should illuminate at full lumen levels when the test switch is depressed regardless of the lumen level during normal operation The entire generator or central ...

Отзывы: