INSTALLATION

WIRING THE BACKUP NANO INVERTER

>  Use the wiring diagram found on page 4 as reference.

>  Connect the AC power source leads (Switched and Unswitched) to the input of the backup nano inverter.

>  Connect the output leads of backup nano inverter to the AC ballast/driver. 

>  Wire the AC ballast/driver with the lamp in accordance with manufactures installation instructions. No ballast/

driver is necessary for single dimmable lamp (under 10VA) application.

>  Make sure all connections are in accordance with the National Electrical Code, Canadian Electrical Code and 

any local regulations.

>  Connect the Test Switch/Charging Indicator Light by matching violet/white and brown/white leads. Mount in 

a readily visible location.

>  In a readily visible location, attach the label “CAUTION–This Unit Has More Than One Power Connection Point. 

To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And DC Power  
Supply (Backup Ballast Inverter Connector) Before Servicing.”

STEP #3

STEP #4

JOIN THE INVERTER CONNECTOR & APPLY POWER

>  After installation is complete, apply AC power and join the blue connector.

>  At this point, power should be connected to both the AC ballast and the backup nano inverter, and the Charg-

ing  Indicator Light should illuminate indicating the battery is charging.

>   A short-term discharge test may be conducted after the backup nano inverter has been charging for 1 hour. 

Charge for 24 hours before conducting a long-term discharge test. 

Refer to OPERATION.

During normal operation, AC power is supplied to the AC ballast/driver through the backup nano inverter and the inverter charges its 
internal battery. Connecting the blue connector wires enables the emergency circuit and supplies power to the  
control/monitor circuit. The backup nano inverter detects AC input line voltage (120 or 277 VAC, 60 Hz) and automatically sets the 
output voltage during emergency mode.

When AC power fails, the backup nano inverter automatically switches to emergency mode, keeping the load illuminated for a 
minimum of 90 minutes. When AC power is restored, the backup nano inverter returns to charging mode. The backup nano inverter 
consists of a low-battery voltage disconnect which is reset when AC power is restored. The unit can also detect an abnormal load 
condition (open or shorted load) during emergency mode operation and will protect the backup nano inverter from damage.

OPERATION

MAINTENANCE

Although no routine maintenance is required to keep the backup nano inverter functional, it should be checked periodically to ensure 
that it is working. The following schedule is recommended:

 

 

1.  Visually inspect the Charging Indicator Light monthly. It should be illuminated.

 

 

2.  Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.

 

 

3.  Conduct a 90-minute discharge test once a year. The lamp should operate for at least 90 minutes.

 
 

! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL !

Содержание ELI-S-10

Страница 1: ...l and auxiliary power supplies and inverter connector of the backup nano inverter before servicing 4 This backup nano inverter is for factory or field installation 5 An AC power source 120 or 277 VAC 60 Hz ahead of any wall switch is required to provide battery charging current 6 Do not install near gas or electric heaters 7 This product is for use in indoor or damp locations where the ambient tem...

Страница 2: ...f the AC ballast driver See Illustration 1 for typical installation and select appropriate mounting method STEP 1 DISCONNECT AC POWER FROM FIXTURE INSTALLATION 2 This product is suitable for field installation with suitable luminaires including LED fluorescent and incandescent luminaires with 0 10V dimming capability The 0 10V dimming capability may not be necessary for luminaires that operate und...

Страница 3: ...r has been charging for 1 hour Charge for 24 hours before conducting a long term discharge test Refer to OPERATION During normal operation AC power is supplied to the AC ballast driver through the backup nano inverter and the inverter charges its internal battery Connecting the blue connector wires enables the emergency circuit and supplies power to the control monitor circuit The backup nano inve...

Страница 4: ...escent or non dimming loads no greater than 10 VA cap off all unused dimming DIM leads separately 2 These connections have been evaluated to comply with requirements for UL1310 Class 2 Power Units WIRING DIAGRAM DRIVER Or BALLAST DIM OUT VIOLET PINK DIM OUT GRAY PINK NEUTRAL OUT RED WHITE HOT OUT RED BLACK ELI S 10 DIM IN VIOLET DIM IN GRAY NEUTRAL IN WHITE Unswitched HOT RED Switched HOT IN BLACK...

Отзывы: