AC Driver
Ground
Neutral
Line
LED -
LED +
Unswitched Line
Neutral
Ground
Wall Switch
Bodine EM Driver
Line
Neutral
Ground
Driver In +
Driver In -
LED Load +
LED Load -
Test
Test Switch -
LED LOAD
ON
BLACK
RED
UL Class 2 Circuits
WIRING DIAGRAMS
NOTE: Emergency driver case and green connector must be grounded
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
NOTE 1:
For short-term testing of the emergency function, the battery must be charged for at least one hour. The emergency driver must be
charged for at least 24 hours before conducting a long-term test.