AC Driver

Ground

Neutral 

Line

LED -

LED +

Unswitched Line

Neutral

Ground

Wall Switch

Bodine EM Driver

Line

Neutral 

Ground

Driver In +

Driver In -

LED Load +

LED Load -

Test 

Test Switch -

LED LOAD

ON

BLACK

RED

UL Class 2 Circuits 

WIRING DIAGRAMS

NOTE: Emergency driver case and green connector must be grounded

EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT

TYPICAL SCHEMATICS ONLY.  MAY BE USED WITH OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.

NOTE 1: 

For short-term testing of the emergency function, the battery must be charged for at least one hour. The emergency driver must be 

charged for at least 24 hours before conducting a long-term test.

Содержание BSL10T3

Страница 1: ...the ambient temperature is 0ºC minimum 55ºC maximum Product is also suitable for installation in sealed and gasketed fixtures Product is not suitable for heated air outlets and wet or hazardous locations Maximum allowable case temp is 65ºC See unit label for Tc measurement location 6 An unswitched AC power source is required 120 277 VAC 50 60 Hz 7 Do not install near gas or electric heaters 8 Do n...

Страница 2: ...This is the current into the blue wire connector 4 Ensure there will be sufficient light output in the end application Estimate the egress lighting illumination levels by doing the following A Find the efficacy of the LED load This can be given by the luminaire manufacture This number will be given in lumens per watt lm w It is the installer s responsibility to validate the luminaire manufacturer ...

Страница 3: ...abels STEP 4 WIRING THE EMERGENCY DRIVER Fixture or Test Monitor Plate 2 Wire Illuminated Test Switch Hex Nut Red Black When AC power fails the emergency driver automatically switches to emergency mode powering the LED load per the rating of the emergency driver for a minimum of 90 minutes When AC power is restored the emergency driver returns to charging mode ABConnect Applying AC power to the un...

Страница 4: ...or is still present then recalibrate the commission value by deactivating the unit Apply AC mains to activate unit and it will recommission itself after one hour 3 Check for Open or Short circuit on the output connections Red 5x Flashes Temperature Product temperature is beyond its rated temperature range 1 Ensure unit is within the rated temperature range stated on the product label 2 Confirm by ...

Страница 5: ...S NOTE Emergency driver case and green connector must be grounded EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY MAY BE USED WITH OTHER DRIVERS CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS NOTE 1 For short term testing of the emergency function the battery must be charged for at least one hour The emergency driver must be charged for at least 24 ho...

Отзывы: