INSTALLATION

2

WIRING REFERENCE TABLE

AWG/COLOR

Emergency Power In

12/Black

Emergency Neutral

18/Gray

Emergency Power Out

12/Red

Normal Power Sense

18/Black

Normal Neutral

18/White

Normal Switch Sense

18/Red

WARNING: TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING. ONLY QUALIFIED 

ELECTRICIANS SHOULD INSTALL THE BLCD-20B.

•   BLCD-20B units shall be installed in accordance with state, local and national electrical codes and  

 

 requirements.

•   BLCD-20B units are designed to attach to a junction box or electrical enclosures that are fitted with a   
 

7/8” diameter opening (standard 1/2”knockout).

•   BLCD-20B units operate with power provided by two sources. Place a warning label on each enclosure    
 

that contains a BLCD-20B unit.

WIRING DIAGRAMS

NORMAL HOT

If required and available,

cut Blue Jumper

Loop to use with
NORMALLY CLOSED:

1) Test switch
2) Fire alarm panel
3) Security panel

4) Other

LOCAL

SWITCHING MEANS

NORMAL/EMERGENCY 

LIGHTING

LOAD

BLCD-20B

NORMAL

NEUTRAL

EMERGENCY

NEUTRAL

RED #18

BLACK #12

WHITE #18

RED #12

GRAY #18

EMERGENCY HOT

NORMAL

LIGHTING

LOAD

BLACK #18

G

N

NORMAL

POWER

GENERATOR

EMERGENCY

PANEL

NEUTRAL BUS 

FOR EMERGENCY PANEL

NEUTRAL BUS 

FOR NORMAL PANEL

NORMAL

PANEL

TRANSFER 

SWITCH

LOAD CONTROL RELAY

NORMAL HOT

If required and available,
cut Blue Jumper
Loop to use with

NORMALLY CLOSED:

1) Test switch
2) Fire alarm panel

3) Security panel
4) Other

LOCAL

SWITCHING MEANS

NORMAL/EMERGENCY 

LIGHTING

LOAD

BLCD-20B

NORMAL

NEUTRAL

EMERGENCY

NEUTRAL

RED #18

BLACK #12

WHITE #18

RED #12

GRAY #18

EMERGENCY HOT

NORMAL

LIGHTING

LOAD

BLACK #18

G

N

NORMAL

POWER

GENERATOR

EMERGENCY

PANEL

NEUTRAL BUS 

FOR EMERGENCY PANEL

NEUTRAL BUS 

FOR NORMAL PANEL

NORMAL

PANEL

TRANSFER 

SWITCH

EMERGENCY

SWITCH

SWITCH BYPASS

Содержание BLCD-20B

Страница 1: ...7 VAC 50 60 Hz LED Driver 20A 120 277 VAC 50 60 Hz Incandescent 10A 120 VAC 50 60 Hz BLCD 20B 03 06 19 DESCRIPTION The BLCD 20B works in conjunction with an auxiliary generator or central inverter system The unit allows lighting control devices for normal lighting to also control emergency lighting installed within the area The BLCD 20B is designed for lighting control in areas where emergency lig...

Страница 2: ...quired and available cut Blue Jumper Loop to use with NORMALLY CLOSED 1 Test switch 2 Fire alarm panel 3 Security panel 4 Other LOCAL SWITCHING MEANS NORMAL EMERGENCY LIGHTING LOAD BLCD 20B NORMAL NEUTRAL EMERGENCY NEUTRAL RED 18 BLACK 12 WHITE 18 RED 12 GRAY 18 EMERGENCY HOT NORMAL LIGHTING LOAD BLACK 18 G N NORMAL POWER GENERATOR EMERGENCY PANEL NEUTRAL BUS FOR EMERGENCY PANEL NEUTRAL BUS FOR NO...

Страница 3: ...STALLING THE OPTIONAL REMOTE ACTIVATION DEVICE The BLCD 20B provides leads for connection of a remote device that can force the unit into the emergency ON mode The leads are in the form of a factory installed jumper loop blue wire on the BLCD 20B When the loop is complete it disables this function Do not cut this jumper unless remote activation is desired The device that provides remote activation...

Страница 4: ...r OFF re connect the wire to the Switch In lead Turn ON the normal circuit breaker The control device now controls both the normal and emergency lighting together STEP 1 Remove the locking nut from the BLCD 20B unit and insert the unit s threaded nipple through the appropriate knockout Tighten the locking nut so that the unit is secured to the j box or enclosure STEP 2 Connect the BLCD 20B to the ...

Отзывы: