EMERGENCY LIGHTING CONTROL UNIT
Installation Instructions
1. Mount only to an approved electrical enclosure.
2. Do not use near gas or electric heaters.
3. Equipment should be mounted in locations and at heights where it will not readily be subjected to
tampering by unauthorized personnel.
4. Use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
5. Do not use this equipment for other than intended use.
6. Ambient temperature range is 32 - 122ºF (0º- 50ºC); Relative humidity range is 5 to 95%, noncondensing.
7. Maximum permitted load - Ballast : 20A @ 120/277 VAC, 50/60 Hz
LED Driver : 20A @ 120/277 VAC, 50/60 Hz
Incandescent: 10A @ 120 VAC, 50/60 Hz
BLCD-20B
03/06/19
DESCRIPTION
The BLCD-20B works in conjunction with an auxiliary generator or central inverter system. The unit allows lighting
control devices for normal lighting to also control emergency lighting installed within the area. The BLCD-20B is
designed for lighting control in areas where emergency lighting fixtures are connected on dedicated emergency light-
ing circuits that are typically ON 24 hours per day. The BLCD-20B allows ON/OFF control of the emergency lighting
along with the normal room lighting to save energy. The intended operation of the BLCD-20B is to guarantee that
the emergency lighting is ON whenever normal power to the controlled circuit is interrupted. While normal power is
present, the BLCD-20B allows control of the emergency lighting by a device such as an occupancy sensor, a relay, a
dimmer, or a wall switch.
WARNING: TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING. ONLY QUALIFIED
ELECTRICIANS SHOULD INSTALL THE BLCD-20B.
SERVICE BY QUALIFIED PERSONNEL ONLY
FOR GENERATOR OR CENTRAL INVERTER SUPPLIED LIGHTING