READ AND FOLLOW ALL SAFETY INSTRUCTIONS

! IMPORTANT SAFEGUARDS !

WHEN USING ELECTRICAL EQUIPMENT, BASIC

SAFETY PRECAUTIONS SHOULD ALWAYS BE 

FOLLOWED, INCLUDING THE FOLLOWING:

SAVE THESE INSTRUCTIONS

THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.  

THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

Bodine © 2018 Signify Holding. All rights reserved.

236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com

443529080202

FLUORESCENT EMERGENCY BALLAST

Installation Instructions

 

1.  To prevent high voltage from being present on red & yellow output leads prior to installation, inverter  

    connector must be open. Do not join inverter connector until installation is complete and AC power is  
    supplied to the emergency ballast.
  2.  This product is for use with one 17 W through 215 W  (2’ - 8’) or two 17 W through 40 W (2’ - 4’) single  
    pin or bipin fluorescent lamps, including standard, energy saving, HO, VHO, and circline fluorescent lamps.
  3.  Make sure all connections are in accordance with the National Electrical Code and any local regulations.
  4.  To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter  
    connector of the emergency ballast before servicing.
  5.  This emergency ballast is for factory or field installation in either the ballast channel or on top of the  
   fixture.
  6.  This product is suitable for damp locations where the ambient temperature for fixture is 0°C minimum,  
    +50°C maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not  
    suitable for heated air outlets and wet or hazardous locations.
  7.  An unswitched AC power source is required (120 or 277 VAC, 60 Hz).
  8.  Do not install near gas or electric heaters.
  9.  Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
    replaceable. Contact the manufacturer for information on service.
 10.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
 11.  Do not use this product for other than intended use.
 12.  Servicing should be performed by qualified service personnel.

CAUTION: 

Verify that all replacement lamp types marked on the installed luminaire are also identified as suit-

able for use with this inverter/charger pack.

B50LP

Ni - Cd

01/08/19

Содержание B50LP

Страница 1: ... Code and any local regulations 4 To reduce the risk of electric shock disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing 5 This emergency ballast is for factory or field installation in either the ballast channel or on top of the fixture 6 This product is suitable for damp locations where the ambient temperature for fixture is 0 C ...

Страница 2: ... at heights greater than 7 17ft 2 2m the level of illumination must be measured in the end application to ensure the requirements of NFPA 101 and local codes are satisfied For installation on top of the fixture wire bundle covers RMC LP may be required by state or local codes These covers are available from the manufacturer as an accessory kit and must be ordered separately Call your local distrib...

Страница 3: ...T Determine the type of AC ballast installed in the fixture Select the appropriate wiring diagram on back to connect the emergency ballast to the AC ballast and lamp s Make sure all connections are in accordance with the National Electrical Code and any local regulations After installation is complete supply AC power to the emergency ballast and join the inverter connector At this point power shou...

Страница 4: ...R ORANGE 277V TEST SWITCH INVERTER CONNECTOR CHARGING INDICATOR B L K B L K HOT 3 LAMP INSTANT START BALLAST WARNING Refer to Table 1 before connecting BLUE BROWN BROWN RED YELLOW YEL BLK BLU WHT BLUE BLUE BLUE RED BLACK WHITE EMERGENCY LAMP 1 LAMP 2 LAMP 3 E M E R G E N C Y B A L L A S T WALL SWITCH WHT RED RED WHITE VIOLET BROWN WHITE WHT BLK COMMON CAP UNUSED LEAD BLACK 120V OR ORANGE 277V TEST...

Страница 5: ... brown connector BROWN BROWN RED YELLOW YEL BLK BLU WHT BLUE CAP CAP CAP CAP E M E R G E N C Y B A L L A S T WHT RED RED WHITE VIOLET BROWN WHITE WHT BLK COMMON CAP UNUSED LEAD BLACK 120V OR ORANGE 277V TEST SWITCH INVERTER CONNECTOR CHARGING INDICATOR B L K B L K HOT E M E R G E N C Y B A L L A S T WALL SWITCH WHT RED RED WHITE VIOLET BROWN WHITE WHT BLK COMMON CAP UNUSED LEAD BLACK 120V OR ORANG...

Отзывы: