5. INSTALLATION
5.1 Mechanical installation
- The terminal is designed for indoor installation only.
- Select premises with low temperature variations and far from any electromagnetic
interference sources (contactors, motors, other badge swipe readers, etc.).
- Open the terminal with the key [A].
- Remove connector [J] and unclip the front panel of the terminal.
- Remove the the protection plate [C] by loosening the 2 screws and by sliding it upwards.
- Fasten the back of the terminal where selected, using the 4 dowel pins and 4 screws
supplied.
5.2 Electrical installation
With the system de-energized, connect the contacts of the relay (230
V, 4A
max
) concentrator block
[B1].
For mains supply
:
After de-energizing the relevant circuit-breaker / disconnecting switch, connect the 230
V
±10%50
Hz mains supply to the concentrator block [B2] (1.5 to 2.5
mm
2
cross-section phase,
neutral and earth wire, bare on a 5
mm length).
For low voltage power supply:
Connect a 12V
DC
(11.5 to 15
V
DC
) power supply to the concentrator block [B4]. Should the external
power supply be equipped with an off-mains operating battery, if necessary, connect the "mains
supply" signal (12
V
DC
= mains supply, 0
V
DC
= no mains supply).
Connect the low voltage power cord of concentrator block [B3] to the external electrical devices
(typically BODET Kar readers). The amperage supplied by the terminal on this concentrator block
is limited to 200
mA. The maximum voltage supplied is 14.5
V
DC
.
Plug connector [H] from back-up battery [I] to the power-supply board.