Maintenance

Decommissioning with refrigerant CO

2

Close shut-off valves at the compressor. CO

2

 does not need to be recycled and can therefore 

be blown off into the environment. It is essential to ensure good ventilation or conduct the CO

2

 

into the outdoors to avoid danger of suffocation. When blowing off the CO

2

, use appropriate 

measures to prevent oil from being carried along with it. 
Loosen  the  fastening  screws  of  the  shut-off  valves  only  when  the  compressor  is 

depressurized. Remove compressor with lifting gear if necessary. If the compressor is to be 

scrapped, the oil must be drained and made available for recycling. Observe environmental 

and national regulations!

 For major repairs or during shutdown: Observe safety instructions, 

 p. 4 and p. 21!

 For major repairs or during shutdown: Observe safety instructions, 

 p. 4 and p. 21!

Close shut-off valves at the compressor. Suction off refrigerant (do not blow off!) and 

dispose of it according to regulations. Loosen the fastening screws of the shut-off 

valves only when the compressor is depressurized. Remove compressor with lifting 

gear if necessary. Dispose of compressor oil according to regulations. Observe national 

regulations! 

Decommissioning with refrigerant R410A

Screwed unions

Different assembly, maintenance and repairs require interferences into the com-

pressor. Any work may be accomplished thereby only considering the initially given 

safety references. The tightening of screws torques are to be considered. 

Current table see support homepage.

R410A

Auszug aus der Schmierstofftabelle

Die im Werk serienmäßig eingefüllte Ölsorte ist auf dem 

Typschild

 vermerkt. 

Diese Ölsorte

sollte bevorzugt eingesetzt werden

. Alternativen dazu sind in nachfolgendem Auszug

aus unserer Schmierstofftabelle aufgeführt. 

Schmierstoffe

Bock-Serienölsorte 

 

Empfohlene Alternativen

Für HFCKWs (z.B. R22)

FUCHS Reniso SP 46

 

MOBIL SHC 425 

SUNOIL Suniso 4GS

 

 

 

SHELL Clavus SD 22-12 

TEXACO Capella WF 46

Für HFKWs (z.B. R 134a, R404A, R407C)

FUCHS Reniso Triton SE 55

  FUCHS SEZ 32 

MOBIL Arctic AL 46

 

 

 

ICI Emkarate RL 46 S 

SHELL Clavus R 46

Auskunft über weitere geeignete Öle auf Anfrage. 

Auszug aus der Schmierstofftabelle

Die im Werk serienmäßig eingefüllte Ölsorte ist auf dem 

Typschild

 vermerkt. 

Diese Ölsorte

sollte bevorzugt eingesetzt werden

. Alternativen dazu sind in nachfolgendem Auszug

aus unserer Schmierstofftabelle aufgeführt. 

Schmierstoffe

Bock-Serienölsorte 

 

Empfohlene Alternativen

Für HFCKWs (z.B. R22)

FUCHS Reniso SP 46

 

MOBIL SHC 425 

SUNOIL Suniso 4GS

 

 

 

SHELL Clavus SD 22-12 

TEXACO Capella WF 46

Für HFKWs (z.B. R 134a, R404A, R407C)

FUCHS Reniso Triton SE 55

  FUCHS SEZ 32 

MOBIL Arctic AL 46

 

 

 

ICI Emkarate RL 46 S 

SHELL Clavus R 46

Auskunft über weitere geeignete Öle auf Anfrage. 

Lubricants

The oil grade filled as standard in the factory is noted on the 

name plate. This oil grade 

should be used preferabley. 

Alternatives to this see following lubricant table.

For enterprise with CO2 the oil support C 55 E is necessary!

HFKW R410A

Information on further suitable oils on request.

Bock standard oil grade

Recommended alternatives

Содержание Pluscom HG34P Series

Страница 1: ...D GB F E I 1 D GB F E I Operating instructions Types HGX34P 215 4 CO2 HGX34P 255 4 CO2 HGX34P 215 4 R410A HGX34P 215 4 S R410A HGX34P 255 4 S R410A HGX34P 315 4 R410A HG34P CO2 R410A up to 40 bar...

Страница 2: ...ressor or refrigerating machine DANGER This symbol refers to instructions for avoiding direct severe dangers to persons DANGER This symbol refers to instructions for avoiding direct severe dangers to...

Страница 3: ...irect start circuit diagram Electronic release unit MP 10 Connection of motor protection unit MP 10 Connection of motor protection unit MP 10 Oil sump heater Information for contactor and motor contac...

Страница 4: ...entation means that they are capable of assessing the work to be carried out and detecting any possible dangers Safety instructions Any handling of the compressor is permissible only by skilled person...

Страница 5: ...etic four cylinder reciprocating compressor with oil pump lubrication Suction gas cooled drive motor Compact dimensions quiet running high efficiency four Use as intended This operating manual describ...

Страница 6: ...les Swept volume Number of cylinders Size Oil filling Series Type code example Electrical accessories can change the IP safety class system Product description Nameplate example 1 Type designation 2 M...

Страница 7: ...C R22 HFKW HFC R134a R404A R507 R407C Oil filling The compressors are filled with the following oil grades in the factory for R22 FUCHS Reniso SP 46 for R134a R404A R407C R507 FUCHS Reniso Triton SE 5...

Страница 8: ...X in the type designation e g HGX34P 315 4 We recommend using the above oil grades for refilling Alternatives see excerpt from the Bock lubricant table page 18 Key to temperatura di evaporazione C tc...

Страница 9: ...overheat the valve Cool the valve body during and after soldering Compressors are lled with protective gas ex works approx 3 bar nitrogen Leave protective gas lling in the compressor up toevacuation D...

Страница 10: ...e immediately after the compres sor is of great importance for the system s smooth running and freedom from vibration Pipe connections The pressure and suction shutoff valves have graduated inside dia...

Страница 11: ...ervice connec tion closed Opening the service connection Turn spindle 1 turn to the right Service connection opened shutoff valve opened Fig schematic Valve spindle seal loosen tighten Fig schematic S...

Страница 12: ...rect protective version see name plate Use strain relief Avoid abrasion points on cables Motor contactors feed lines and fuses are to be rated according to the maxi mum operating current see compresso...

Страница 13: ...tart Y Start 400 V Y only direct start Elektrischer Anschluss Electrical connection Raccordement lectrique Y 96027 11 06 DGbF Niedere Spannung Low voltage Bas voltage Y Hohe Spannung High voltage Haut...

Страница 14: ...Trigger unit MP10 E Oil sump heating X3 Terminal block in terminal box Electrical system Circuit diagram direct start 230 V 400 V Y MP10 1 2 Connections for PTC sensor R1 PTC sensor motor winding R2 H...

Страница 15: ...D GB F E I 15 Terminal box compressor A1 Alarm motor protection A2 Temperature rise R1 R2 A3 Alarm high pressure X SS Terminal strip switch cabinet...

Страница 16: ...rrupting the mains power with the external alarm reset switch S1 see main line wiring diagram The reclosure preventing feature is unlocked and LEDs H1 or H2 go off again Electrical system In addition...

Страница 17: ...y contact of the compressor contactor to a seperate electric circuit El data 110 240 V 1 50 60 Hz 50 120 W PTC heating adjusting In order to avoid damage to the compressor the compressor is equipped w...

Страница 18: ...s Verdichters nicht berschritten werden siehe Typschildangabe Dichtheitspr fung Dichtheitspr fung Dichtheitspr fung der K lteanlage Dichtheitspr fung der K lteanlage gem EN 378 2 oder einer entspreche...

Страница 19: ...treffen z B Druckhaltek lteanlage oder Hochdruck stufe der Kaskade betreiben Eine nach Inbetriebnahme erforderlich werdende K ltemittelerg nzung kann gasf r mig in die Saugseite eingef llt werden ber...

Страница 20: ...t be properly designed All components must be rated to be compatible with each other with regard to output particularly evaporator and expansion valve Suction gas overheating at the compressor entranc...

Страница 21: ...3 years or 10 000 12 000 operating hours Dispose of old oil according to the regulations observe national regulations Regular checks Oil level tightness running noise pressures temperatures func tion...

Страница 22: ...ightening of screws torques are to be considered Current table see support homepage R410A Auszug aus der Schmierstofftabelle Dieim Werk serienm ig eingef llte lsorteist auf dem Typschild vermerkt Dies...

Страница 23: ...tage Max working current Y Max power consump tion Starting current rotor blo cked Y Discharge line DV Suction line SV m 3 h A kW A kg mm inch mm inch Ltr HGX34P 215 4 CO 2 4 18 80 22 60 32 4 18 7 11 1...

Страница 24: ...8 HGX34P 215 4 S R HGX34P 255 4 S R HGX34P 315 4 R41 Anschl sse Connections SV Saugabsperrventil Rohr L Suction line valve tube DV Druckabsperrventil Rohr L Discharge line valve tube A Anschlu Saugsei...

Страница 25: ...rective 98 37 EEC annex II B We herewith declare that the hermetic refrigerating compressors named in the title in the version supplied by us are intended for installation in a machine which complies...

Страница 26: ...26 D GB F E I...

Страница 27: ...D GB F E I 27...

Страница 28: ...Kunde Bock Verdichter sind hochwertige zuver Vorteile in vollem Umfange und ber den k nnen beachten Sie unbedingt die folg Montage Betrieb und Zubeh r wenden S K ltefachgro handel bzw unsere Vertret...

Отзывы: