
D
GB
F
E
19
96571-08.2022-DGb
Relay position INT69 G
B2 12 14 11
Fig. 16
5
|
Electrical connection
Gauge state
Relay position
1.
Deactivated state
11-12
2.
INT69 G switch-on
11-14
3.
Remove PTC connector
11-12
4.
Insert PTC connector
11-12
5.
Reset after mains on
11-14
5.7 Oil sump heater
In order to avoid damage to the compressor, the compressor has to be equipped with an oil sump heater.
Operation:
The oil sump heater operates when the compressor is at a standstill.
When the compressor starts up, the oil sump heating switches off.
Connection:
The oil sump heater must be connected via an auxiliary contact (or parallel wired auxiliary
contact) of the compressor contactor to a separate electric circuit
.
Electrical data: 220 - 240 V - 1 - 50/60 Hz, 80 W.
ATTENTION The oil sump heater must generally be connected and operated!
For safe operation of the compressor, the frequency converter must be able to apply an overload of
at least 160% of the compressor's maximum current (I-max.) for at least 3 seconds.
When
using frequency converters
, the following things must also be observed:
1. The maximum permissible operating current of the compressor (I-max) (see type plate or
technical data) must not be exceeded.
2. If abnormal vibrations occur in the system, the affected frequency ranges in the frequency
converter must be blanked out accordingly.
3. The maximum output current of the frequency converter must be greater than the maximum
current of the compressor (I-max).
4. Carry out all designs and installations in accordance with the local safety regulations and
common rules (e.g. VDE) and regulations as well as in accordance with the specifications of the
frequency converter manufacturer
The permissible frequency range can be found in the technical data chapter 8, p. 26.
5.8
Selection and operation of compressors with frequency converters
f-min/f-max see chapter 8: Technical data: permissible frequency range.
Rotational speed
range
0 - f-min
f-min - f-max
Start-up time
< 1 s
ca. 4 s
Switch-off time
immediately