background image

appliances in the space. Each opening shall have an area of not less than 100 square inches or
a minimum dimension of not less than 3 inches.

B. Outside Air Supply:

Confined spaces shall be provided with two permanent openings;

one within 12 inches of the top and one within 12 inches of the bottom of the enclosure.
These openings shall communicate directly, or by ducts, with the outdoors or spaces that
communicate with the outdoors.

1. Leading directly to the outside or through vertical ducts:

Each opening shall have a

minimum free area of one square inch per 4000 Btu/hr of total input rating of all equip-
ment in the enclosure.

2. Leading to outside through horizontal ducts:

Each opening shall have a minimum free

area of one square inch per 2000 Btu/hr of total input rating of all equipment in the
enclosure.

Note:

All ducts shall have the same cross sectional area as the free area of each

opening to which they connect. The minimum dimensions of all ducts shall not be less
than three inches. Powered combustion air supplies are also commercially available and
may be used.

LOUVERS & GRILLES

In calculating the free area of an opening, consideration must be given to the blocking effects
of louvers or grilles protecting the opening. Any screens used must be no finer than

1

4

inch

mesh. If the free area of a louver or grille is known, this should be used in calculating the size
of opening required. If free area is unknown, it may be assumed that wood louvers will have
20 to 25% free area and metal louvers and grilles will have 60 to 75% free area. Louvers and
grilles should be fixed in the open position or interlocked with the equipment so that they
open automatically during equipment operation.

VENTING

The water heater shall be located as close to the chimney as practical. Long lateral runs will
result in intermittent combustion problems and unsafe operating conditions. Total vent
height should be a minimum of 6 feet. Shorter vent heights could result in unstable draft and
nuisance lock outs.

The venting system should be sized according to National Fuel Gas Code: NFPA 54/ANSI
Z223.1 (most recent edition) using the “Fan Min, Max” columns. If you do not have a copy of
this code one can be obtained at www.NFPA.org for a nominal fee. Copies of the NFPA venting
tables are also reprinted in the Bock Engineering Manual available from your Bock Represen-
tative or download from www.bockwaterheaters.com.

Note:

Do not reduce vent size more

than one size smaller than the vent connector supplied with the heater. B vent, L vent or
multi-fuel chimneys may be used. Single wall vent connectors may also be used.

When connecting to an existing vent system, examine the piping and system for condition.
Replace any sections that show signs of significant corrosion or have become perforated. Also
verify that the system is of the correct type and sized properly for the water heater and any
other appliances that are connected to it. Correct any discrepancies found between the exist-
ing system and current NFPA 54 code.

Draft must be controlled with a barometric damper or draft regulator approved for gas appli-
ances, normally supplied with each complete Bock Water Heater.

(This device differs from a

vent/flue damper in that it precisely regulates the amount of room air entering the vent to control
draft. A vent/flue damper shuts off the vent during stand by periods to reduce losses and has no
effect of draft.)

The draft regulator may be installed in a tee on top of the water heater and

must be adjusted while the water is running to regulate draft to a minimum of –0.02 inches
water column (WC) and a maximum of –0.05" WC. Draft over the fire should be slightly nega-
tive. Draft is normally adjusted by hanging washers (supplied with the draft regulator) on the
draft regulator chain. Follow the instruction supplied with the draft regulator for proper loca-
tion and draft adjustment procedures.

Note:

Failure to install the barometric damper or adjust

draft properly will result in unsafe operating conditions and nuisance burner lock outs.

Power Gas

Page 5

Содержание 50 ESPG

Страница 1: ...water temperature is needed in part of the water system automatic temperature limiting devices must be used on all lines to water taps WARNING Flammable vapors may be drawn to this water heater from...

Страница 2: ...N A 171 4 120 60 270 40 PG 40 126 1 2 3 4 3 4 1 90 134 61 20 6 54 18 120 60 295 50 ESPG 50 140 1 2 1 11 2 11 2 90 142 52 26 6 131 2 181 2 120 60 345 51 PG 50 152 1 2 1 1 3 4 90 159 59 24 6 11 18 120 6...

Страница 3: ...separate units The aquastat and immersion well are packed with the burner If damage is observed or parts appear to be missing contact your wholesaler A burner installation and setup manual is also pac...

Страница 4: ...upply will result in poor burner water heater performance and nuisance lock outs Unsafe levels of carbon monoxide CO conden sation and sooting may result if the room does not have an adequate air supp...

Страница 5: ...et Shorter vent heights could result in unstable draft and nuisance lock outs The venting system should be sized according to National Fuel Gas Code NFPA 54 ANSI Z223 1 most recent edition using the F...

Страница 6: ...by the decal shown on the left The purpose of this bushing is to help keep the tank bottom free of sediment by aiding tank flushing This bushing must be located as shown on the decal to function prop...

Страница 7: ...test Edition For LP installations refer to NFPA 58 latest edition for proper gas piping Supply piping should be sized according to the charts found in the National Fuel Gas Code for natural gas applic...

Страница 8: ...pm 0 preferred O2 should be between 3 and 6 3 5 is preferred for Carlin and Midco burners see burner manual for more detail Note Your Bock Power Gas Water Heater system may produce 80 to 120 ppm CO an...

Страница 9: ...se accumulations can be controlled to an extent by softening the water or using other water treatment systems The tank should be inspected every six months Drain remove the hand hole cover and make a...

Страница 10: ...ration at 110 S Dickinson Street Madison Wisconsin 53703 Company warrants to the owner the tank of this water heater will not leak due to defective materials or workmanship for FIVE 5 years from the d...

Страница 11: ...removal of the magnesium anode rods noise odor rusty water the installation of an insulation blanket installation outside of the United States excluding Canada or on which the serial numbers have bee...

Страница 12: ...64 3 5 WC 7 3 5 WC 71PG 173 000 EC200 9 NONE 3 5 WC 3 3 5 WC 190PG 190 000 EC300 3 5 5 16 3 5 WC 2 3 5 WC 72PG 199 000 EC300 4 5 P 3 5 WC 1 3 5 WC 73PG 242 000 EC300 5 W 3 5 WC G 3 5 WC 241PG 277 000...

Отзывы: