3. MOUNTING INSTALLATION
3.1
CEILING MOUNTING
The heater is intended for installation in a suspended ceiling mounted within or on the 'tee' bar supports. For optimum results do not fit in ceilings
higher than 3m. As air is only introduced through the front of the unit the heater may be sighted anywhere. The air intake and discharge areas must
be kept completely clear for a minimum of 1.5m from the front of the heater. In an area using multiple units, heaters should be spread to provide an
even heat distribution.
IMPORTANT!
A minimum clearance of 205mm is needed between the bottom of the false ceiling and the original roof/ceiling to allow
installation of the heater.
IMPORTANT!
DO NOT use plastic type diffusers as these may be damaged by the heat.
IMPORTANT!
Ensure that the mounting surface / ceiling supports are capable of taking the additional weight of the heater there are 2 eye
hooks supplied with the heater that should be used if additional support of the heater is required.
When using the diffuser the four Z brackets provided should be attached to the side of the heater to enable the heater to be supported by the 'tee'
bar and immediately above the diffuser.
4. ELECTRICAL CONNECTIONS
4.1 230V SINGLE PHASE
– Without controls.
Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing.
Drawings show connections inside the black terminal box on the outside of the heater.
Do NOT use power tools to undo or do up terminal screws.
Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes.
Standard Connection and Use
Use 2.5mm² 3 Core Mains Cable (see note above).
Connect Brown wire
– Terminal 1 or L.
Connect Blue wire
– Terminal 5 or N.
Connect Green / Yellow wire
– Terminal E or
Ensure the 3 links
are in position between terminals 1 and 2, 2 and 3, 3 and 4
as shown in drawing to the left.
If you wish to de-rate the heater from 4.5kW to 2.25kW remove the link
between
terminal 3 and terminal 4. Ensure you tighten up the screws after removing the link. See
drawing to the right.
PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE
4.2 230V SINGLE PHASE
– With Thermostat (RST-TP).
Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing.
Drawings show connections inside the black terminal box on the outside of the heater and the inside of the RST-TP Thermostat. Other thermostats
may be used BUT they must be suitable for a 4.5kW load.
Do NOT use power tools to undo or do up terminal screws.
Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes.
Standard Connection using RST-TP Thermostat
Use 2.5mm² 3 Core Mains Cable (see note above)
Use 2.5mm² 4 Core Cable to connect the heater to the
thermostat (see note above).
Remove link
in heater terminal box between
terminals 1 and 2.
Ensure the remaining 2 links are in position between
terminals 2 and 3, 3 and 4 as shown in drawing to the left.
Mains Cable
Connect Brown wire
– Terminal 1 or L.
Connect Blue wire
– Terminal 5 or N.
Connect Green / Yellow wire
– Terminal E or
Heater to Thermostat Cable
– (Colours for reference only)
Connect Brown wire
– Terminal 1 or L of heater and
Terminal 3 of Thermostat.
Connect Grey wire
– Terminal 2 of heater and Terminal 1
of Thermostat.
Connect Blue wire
– Terminal 5 or N of heater and
Terminal 4 or N of Thermostat.
Connect Green / Yellow wire
– Terminal E or
of the
heater and earth connection on Thermostat.
If you wish to de-rate the heater from 4.5kW to 2.25kW remove the link
between terminal 3 and terminal 4. Ensure you tighten up the
screws after removing the link.
PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE