This product conforms to EU Directive 2002/96/EC.
This appliance bears the symbol of the crossed waste bin. This indicates that, at the end of its useful life, it must not be disposed of as domestic
waste, but must be taken to a collection centre for waste electrical and electronic equipment. It is the user's responsibility to dispose of this appliance
through the appropriate channels. Failure to do so may incur penalties established by laws governing waste disposal.
BN Thermic Ltd,
34 Stephenson Way,
Crawley, RH10 1TN
Tel: +44 (0) 1293 547361
Email: [email protected]
Web: www.bnthermic.co.uk
3. MOUNTING INSTALLATION
3.
1 WALL MOUNTING (see Fig.1)
❑
IMPORTANT!
The following points should be noted:
The heater should always have a
minimum clearance of 450mm from a ceiling and be at least 1M from any object (see table
on front page).
❑
IMPORTANT!
Ensure that the mounting surface is capable of supporting the weight of the heater.
❑
IMPORTANT!
The heater should be mounted at 30º to 45º from the vertical.
❑
IMPORTANT!
The mounting bracket must be sufficiently earthed.
3.1.1 Before drilling, ensure that there are no wires or water pipes in the area where the heater is to be
placed.
3.1.2 Use the bracket as a template. Fix the metal bracket to the wall by means of the three holes and
appropriate fixings (not supplied).
3.1.3 Refit the heater onto the bracket with the bolt provided.
3.1.4 Adjust the angle of heater to direct heat where required, between 30° and 45° (see Fig.1).
3.2 CEILING MOUNTING
3.2.1 An optional pack containing 4 hooks and nuts is available from your supplier to enable the heater
to be ceiling mounted on suitable chains.
3.2.2 Insert these 4 hooks into the M6 threaded holes in the back corners of the heater and lock in
place with the supplied nuts.
3.2.3 Heaters can be hung horizontal to the floor or at an angle. If hung at an angle this should be
ideally be 30º to 45º making sure the ceramic element remains in a horizontal position to the floor.
4. ELECTRICAL CONNECTIONS
4.1
230V INSTALATION
4.2
Please make sure you have read the Safety instructions and you are a suitably qualified
electrician before continuing.
4.3
This heater is factory fitted with high temperature silicon rubber flexible cable conforming to
BS6500 having a temperature rating of 180°C.
4.4
Heaters must be earthed.
4.5
Connection to a Switched Fused Spur / Isolator.
a) Connect the GREEN/YELLOW earth wire to the earth connection.
b) Connect the BROWN live wire to the live
connection.
c) Connect the BLUE neutral wire to the
neutral connection.
d) After wiring, check that there are no bare
wires, that all wires have been correctly
connected, that the cable outer insulation
extends beyond the cable restraints and
that the restraint is tight.
5. COMMISSIONING
Note:
The Heater runs hot so please wait till it has cooled down before moving / adjusting.
WARNING! Ensure you read, understand and apply the safety instructions in Section 1 before using the heater.
5.1 Perform insulation and earth continuity tests.
5.2 Switch on the heater(s) and confirm that the ceramic element is working.
5.3 Ensure each heater aims its warmth into the target area by adjusting the heaters angle as required, and then tighten the bracket bolts keeping
the heater firmly in place while doing so.
5.4 Make sure you maintain an angle between 30º & 45º in the vertical plane.
5.5 The user / customer should be made aware of all aspects of the operation and safety advice. Keep the instructions safely for future reference.
5.6
In unoccupied premises it is recommended that the heating system is switched of and isolated from the electrical supply.
6. MAINTENANCE
Note:
Before examining or carrying out any maintenance ensure the heater has cooled down and is disconnected from the mains supply.
6.1
Ceramic Heaters contain no moving parts and therefore very little maintenance is required other than to ensure that there is no excessive
build-up of dust / dirt on the reflectors or ceramic elements especially after a long period of non-use as this can cause overheating and
premature ceramic failure. Depending on installation conditions the heater should be regularly inspected, but at least once per year.
Spare ceramic elements and reflectors are available contact your supplier for details
NOTE: It is our policy to continually improve products and as such we reserve the right to alter data,
specifications and component parts without prior notice.
IMPORTANT:
No liability is accepted for incorrect use of this product.
WARRANTY:
Your BN Thermic product is guaranteed for one year from date of purchase. We will repair or
replace at our discretion any part found to be defective. We cannot assume any consequential liability. This
guarantee in no way prejudices your rights under common law and is offered as an addition to consumer
liability rights.
REGISTER:
Activate your warranty by registering online at www.bnthermic.co.uk and retain this installation
data for future reference.
CH2-15INS-v01