background image

Installation

 Instructions

 ESS 

7

.0

3

 

Initial Installation

 

Connecting the Energy Storage Unit

1.

STEP ONE

:

Connect the two 

 

cables of the

 

ESS

7

.0

.  C

onnect according to the

 

Inverter

manufacturer (eg: SMA 

Sunny

 

Island)

.

2.

Red = 

P

ositive 

T

erminal

3.

BLACK = NEGATIVE

2.

STEP TWO

:

Connect the p

atch

 

cable

 

(RJ45)

 

supplied by the inverter mfg. 

to 

the 

CAN connector

 position  on 

the  ESS 

storage  unit,  from  the  Inverter 

(eg. SMA 

Sunny I

sland Inverter)

3.

 

STEP THREE

:

Place the t

ermination connector to the 

socket labeled "Internal"

 

patch

 (Intern)

.  

If installing multiple units, place this 

connector in the last unit.

4.

STEP FOUR

:

Use  NH1  fuses,  according  to  the 

permissible  loading  currents  of  the 

inverter  (eg. 

SMA  Sunny  Island) 

and close 

fuse

 isolators.

Recommended Fuses;

SI3.0M-11: 

80A 

SI4.4M-11: 

100A 

SI6.0H-11: 

160A 

SI8.0H-11: 

200A

 (included)

Содержание ESS 7.0

Страница 1: ...EUROPE S LEADING BATTERY SYSTEM SUPPLIER NOW SERVING NORTH AMERICA INSTALLATION INSTRUCTIONS ESS 7 0 Revised 12 1 2015 ...

Страница 2: ...her object è Short Circuit è Danger SYMBOLS WARNING Possible electric shock fire or explosion Explosion can cause serious injury This product is applicable to EC directives Europe Only The product must not be disposed of with household waste countries must be disposed of in an appropriate facility Do not expose the energy storage unit to rain or moisture or direct sunlight Battery System Manual Us...

Страница 3: ...d by the inverter mfg to the CAN connector position on the ESS storage unit from the Inverter eg SMA Sunny Island Inverter 3 STEP THREE Place the termination connector to the socket labeled Internal patch Intern If installing multiple units place this connector in the last unit 4 STEP FOUR Use NH1 fuses according to the permissible loading currents of the inverter eg SMA Sunny Island and close fus...

Страница 4: ...t 5 44 kWh Max Discharge Current 300A 3sec Protection IP 21 Possible Loading Operational Range 0 to 45 C Power Connection 2 cables 50mm M8 Dimensions WxLxH 25 x17 8 x16 5 638x452x420 mm Weight 209lbs 95 kg Namplate LED Indicator Turn On Press push button for 1 second then release actual image may vary 5 STEP FIVE You can now use the inverter eg SMA Sunny Island according to the manufacturer s spec...

Страница 5: ...the energy storage unit is connected to the system Clean housing parts with a clean dry cloth Excessively high temperatures within the energy storage unit are cooled by a built in fan that is automatically activated A constant red LED on the energy storage unit indicates the device needs to be serviced Disposal Battery energy storage unit may not be disposed of with household waste The energy stor...

Отзывы: