INSTALLATION AND OPERATING INSTRUCTIONS · HSI
EN
• Be sure to keep other objects and surfaces as shown in the below diagram to guarantee
sufficient heat dissipation and to have enough space for removing wires .
☝
NOTE!
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE
ONLY.
Install the unit by screwing three screws .
Battery Connection
⚠
CAUTION!
To safety operation and regulation compliance, it’s requested to install a separate DC
over-current protector or disconnect device between battery and inverter . It may not be
requested to have a disconnect device in some applications, however, it’s still requested to
have over-current protection installed . Please refer to typical amperage in below table as
required fuse or beaker size .
ѥ
WARNING!
All wiring must be performed by a qualified personnel .
ѥ
WARNING!
It's very important for system safety and efficient operation to use
appropriate cable for battery connection . To reduce risk of injury,
please use the proper recommended cable and terminal size as
below .
Figure 6:
2 kVA – 3 kVA
Figure 7:
Ring Terminal