User Manual of String Inverter
18
3.4 Requirements for reserved space
When installing string inverters, proper space must be reserved around the string inverters to
facilitate heat dissipation and maintenance.
≥
500mm
≥
300mm
≥
500mm
≥
200mm
≥
10
00
mm
Figure 3-1 Installation space of string inverter
When multiple string devices are installed on the same plane, it is recommended to install in a
straight line.
≥
200mm
≥
200mm
Figure 3-2 Installation space of string inverter
If you need to install it in two rows, it is recommended to install them in the shape of triangle.
≥
100mm
≥
300mm
≥
100mm
≥
300mm
Figure 3-3 Installation space of string inverter
16