Blueridge BMHH09Y25 Скачать руководство пользователя страница 29

 

 

 

Outdoor Unit 

Installation

 Page 28

 

Step 4: Connect signal and power cables

The outside unit’s terminal block is protected by 

an electrical wiring cover on the side of the unit. 

A comprehensive wiring diagram is printed on 

the inside of the wiring cover.

 WARNING

 

 

 

 

 

 

 

 

 

 

1. Prepare the cable for connection:

USE THE RIGHT CABLE 

• 

Indoor Power Cable (if applicable):  H05VV-F 

or H05V2V2-F

• 

Outdoor Power Cable:  H07RN-F

• 

Signal Cable:  H07RN-F

a.  Using wire strippers, strip the rubber 

jacket from both ends of cable to reveal 

about 40mm (1.57in) of the wires inside.

b.  Strip the insulation from the ends of the 

wires.

c.  Using a wire crimper, crimp u-lugs on the 

ends of the wires.

PAY

 ATTENTION TO LIVE WIRE

While crimping wires, make sure you clearly 

distinguish the Live (“L”) Wire from other wires.

 

2. Unscrew the electrical wiring cover and remove it.

3. Unscrew the cable clamp below the terminal

    block and place it to the side.

4. Connect the wire according to the wiring 

    diagram, and firmly screw the u-lug of each 

    wire to its corresponding terminal.

5. After checking to make sure every connection is 

    secure, loop the wires around to prevent rain 

    water from flowing into the terminal.   

6. Using the cable clamp, fasten the cable to the

    unit. Screw the cable clamp down tightly.

7. Insulate unused wires with PVC electrical tape.

    Arrange them so that they do not touch any

    electrical or metal parts.

8. Replace the wire cover on the side of the unit,

    and screw it in place.    

1. Remove the wire cover from the unit by 
    loosening the 3 screws.
2. Dismount caps on the conduit panel.
3. Temperarily mount the conduit tubes(not 
    included) on the conduit panel.
4. Properly connect both the power supply and 
    low voltage lines to the corresponding 
    terminals on the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches
    longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.
      

BEFORE PERFORMING ANY ELECTRICAL
OR WIRING WORK, TURN OFF THE MAIN
POWER TO THE SYSTEM.

 WARNING

ALL WIRING WORK MUST BE PERFORMED 
STRICTLY IN ACCORDANCE WITH THE 
WIRING DIAGRAM LOCATED INSIDE OF 
WIRE COVER OF THE OUTDOOR UNIT .

 

 

 

 

 

 

 

 

 

 

 

 

 

CHOOSE THE RIGHT CABLE SIZE

In North America

The size of the power supply cable, signal cable, 
fuse, and switch needed is determined by the 
maximum current of the unit. The maximum 
current is indicated on the nameplate located on
the side panel of the unit. Refer to this nameplate 
to choose the right cable, fuse, or switch.     

Cover

Screw

G

Wire Cover 

Over 1.57in.(40mm)

Terminal block

Conduit panel

Connecting cable 

Power supply cord 

Please select the appropriate through-hole according
to the diameter of the wire.

Содержание BMHH09Y25

Страница 1: ...before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and manufacturer informa...

Страница 2: ...Owner s Manual Table of Contents Safety Precautions 03 Care and Maintenance 11 Troubleshooting 13 1 Indoor unit display 07 2 Operating temperature 08 3 Other features 09 4 Setting angle of airflow 10...

Страница 3: ...t indoor unit 24 Outdoor Unit Installation 25 1 Select installation location 25 2 Install drain joint 26 3 Anchor outdoor unit 26 4 Connect signal and power cables 28 Refrigerant Piping Connection 29...

Страница 4: ...like a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into th...

Страница 5: ...hare the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection device which has...

Страница 6: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Страница 7: ...hanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be re fabricated IEC Standard Requirements European Disposal Guidelines...

Страница 8: ...TIMER OFF is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned off when defrosting cooling heating units when anti cold air feature is turned on when unit is self cleaning when 8 C heati...

Страница 9: ...2 F 15 C 30 C 5 F 86 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Страница 10: ...will increase an additional 1 C 2 F after another hour When in HEAT mode the unit will decrease the temperature by 1 C 2 F after 1 hour and will decrease an additional 1 C 2 F after another hour Slee...

Страница 11: ...of air flow To operate your unit manually 1 Open the front panel of the indoor unit 2 Locate the MANUAL CONTROL button on the right hand side of the unit 3 Press the MANUAL CONTROL button one time to...

Страница 12: ...an the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter lift it up then pull it towards yourself 3 Now pull the filter out 4 If your filter...

Страница 13: ...If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the...

Страница 14: ...Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may o...

Страница 15: ...customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following po...

Страница 16: ...oor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 17: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote co...

Страница 18: ...Mounting Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 1 83m 72in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in t...

Страница 19: ...requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Страница 20: ...direct sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipi...

Страница 21: ...in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Right rear wall hole 65mm 2 5in Right rear wall hole 65mm 2 5in Right rea...

Страница 22: ...extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By default the drain hose...

Страница 23: ...mly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire Do not let wires touch or rest against refrigerant tubing the compressor or any moving...

Страница 24: ...on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can lea...

Страница 25: ...e unit snaps onto the hooks along the bottom of the mounting plate 7 Again check that the unit is firmly mounted by applying slight pressure to the left and the right hand sides of the unit If refrige...

Страница 26: ...wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or sn...

Страница 27: ...bber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain j...

Страница 28: ...led holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DRI...

Страница 29: ...lamp down tightly 7 Insulate unused wires with PVC electrical tape Arrange them so that they do not touch any electrical or metal parts 8 Replace the wire cover on the side of the unit and screw it in...

Страница 30: ...et substances or gases other than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrig...

Страница 31: ...rs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve...

Страница 32: ...0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the pa...

Страница 33: ...for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Страница 34: ...0Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump Li...

Страница 35: ...ethod Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using...

Страница 36: ...he pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe...

Страница 37: ...supply with system impedance no more than 0 281 In case necessary please consult your supply authority for system impedance information This appliance MS11M 18HRN1 QC9 can be connected only to a supp...

Страница 38: ...specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service w...

Отзывы: