NOTE: DO NOT intertwine signal cable with

other wires. While bundling these items

together, do not intertwine or cross the signal

cable with any other wiring.

Refrigerant Piping 

Connection

Page 13 

Fig 7.8

Torque Requirements

Outer Diameter of Pipe (inch)

Tightening Torque (ft/lb)

Add. Tightening Torque (ft/lb)

1/4"

11 ft/ lb

11.8 ft/ lb

3/8"

18.4 ft/ lb

19.18 ft/ lb

1/2"

25.8 ft/ lb

26.55 ft/ lb

5/8"

33.19 ft/ lb

34.67 ft/ lb

NOTE: Use both a spanner and a torque

wrench when connecting or disconnecting

pipes to/from the unit.

NOTE ON MINIMUM BEND RADIUS

Carefully bend the tubing in the middle 

according to the diagram below. 

DO NOT 

bend the tubing more than 90° or more 

than 3 times.

Bend the pipe with thumb

min-radius 3.9”

6.  After connecting the copper pipes to the 

indoor unit, wrap the power cable, signal 

cable and the piping together with binding 

tape.

7.  Thread this pipeline through the wall and 

connect it to the outdoor unit.

8.  Insulate all the piping, including the valves of 

the outdoor unit.

Fig 7.7

CAUTION

•  Fully wrap insulation around the piping. 

Direct contact with the bare piping may 

result in burns or frostbite.

•  Make sure the pipe is properly 

connected. Over tightening may 

damage the bell mouth and under 

tightening may lead to leakage.

Содержание BM18M23C

Страница 1: ...ual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installi...

Страница 2: ...Table of Contents Installation Manual Safety Precautions 04 Accessories 05 Installation Overview 06 Specifications 07 Outdoor Unit Installation 08 1 5 2 3 4...

Страница 3: ...erant Piping Connection 11 Test Run 22 Using the Automatic Wiring Piping Correction Function 23 Wiring 14 Wiring Diagrams 16 Refrigerant Handling 19 Procedure 19 Refrigerant chart 21 Adding refrigeran...

Страница 4: ...it consider strong winds typhoons and earthquakes that might affect your unit and locate it accordingly 7 Do not use means to accelerate the defrosting process or to clean other than those recommended...

Страница 5: ...selecting a suitable remote controller Name Shape Quantity Installation plate 1 Plastic expansion sheath 5 8 depending on models Self Tapping Screw A ST 3 9X25 5 8 depending on models Drain joint some...

Страница 6: ...llation Overview INSTALLATION ORDER MC MC L N Install the indoor unit separate manual Install the outdoor unit Page 09 Connect the refrigerant pipes Page 12 Connect the wires Page 14 Perform a test ru...

Страница 7: ...t feet 2 Zone 3 Zone 4 Zone 5 Zone Max length for all rooms 131 197 262 262 Max length for one indoor unit 82 98 115 115 Max height different between indoor and outdoor unit 49 49 49 49 Max height dif...

Страница 8: ...bolts M10 The area must be free of combustible gases and chemicals The pipe length between the outdoor and indoor unit may not exceed the maximum allowable pipe length If possible avoid installing the...

Страница 9: ...View All Condensers A B mount point dimensions W H W H A B D 10 feet or more 2 feet or more 5 feet or more 10 inches or more Model W D H A B BM18M23C 33 27 14 29 27 64 21 3 13 8 BM27M23C 37 2 16 5 31...

Страница 10: ...e in the bas pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode You must drill a h...

Страница 11: ...t leakage after completing the installation work Step1 Cut pipes When preparing refrigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and minimize the n...

Страница 12: ...shown in table 7 1 Step 4 Connect pipes Connect the copper pipes to the indoor unit first then connect it to the outdoor unit You should first connect the low pressure pipe then the high pressure pip...

Страница 13: ...nit NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below DO NOT bend the tubing more than 90 or more than 3 times Bend the pipe with thumb min radius 3 9...

Страница 14: ...ctrical shock Ensure that main supply connection is made through a switch that disconnects all poles with contact gap of a least 3mm 0 118 DO NOT modify the length of the power cord or use an extensio...

Страница 15: ...s consult an electrician c Using wire strippers strip the rubber jack et from both ends of signal cable to reveal about 6 of wire d Strip the insulation from the ends of the wires e Using a wire crimp...

Страница 16: ...ures if end users wish to perform their own wiring Run the main power cord through the lower line outlet of the cord clamp ____ This symbol indicates field wiring Wiring TO A 1 2 3 TO B 1 2 3 L1 L2 1...

Страница 17: ...3 A 1 B 2 B 3 B 1 C 2 C 3 C L1 L2 1 A 2 A 3 A Ground POWER TO A 1 2 3 TO B 1 2 3 TO C 1 2 3 TO D 1 2 3 1 B 2 B 3 B 1 C 2 C 3 C 1 D 2 D 3 D L1 L2 1 A 2 A 3 A 1 B 2 B 3 B 1 C 2 C 3 C 1 D 2 D 3 D L1 L2 1...

Страница 18: ...Revised 5 14 2020 Wiring TO E 1 2 3 TO C 1 2 3 TO D 1 2 3 TO A 1 2 3 TO B 1 2 3 Ground POWER 1 A 2 A 3 A 1 B 2 B 3 B 1 C 2 C 3 C 1 D 2 D 3 D 1 E 2 E 3 E L1 L2 Page 18 BM48M five zone condenser...

Страница 19: ...ectrical capacity is sufficient Confirm that starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate Confirm that the cable thickness is as specified in th...

Страница 20: ...manifold gauges Pressurize lineset to 200 psi of dry nitrogen 4 Check for leaks Spray soap bubbles on fit tings at outdoor and indoor units to check for bubbles leaks If leaks are present retorque fla...

Страница 21: ...gauges in place Follow the remaining steps to test run the system and add refrigerant if needed 12 Record Pressure Start the unit in cooling mode Run for 10 minutes and monitor oper ating pressure re...

Страница 22: ...igerant charging must be performed after wiring leak testing and vacuuming DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system Doing so can damage the unit or impact i...

Страница 23: ...nnected h Length of the piping and additional refrigerant stow capacity have been recorded i The power voltage is the correct voltage for the air conditioner 1 Open both the liquid and gas stop valves...

Страница 24: ...piping error is corrected and all wiring piping is properly connected 1 Check that outside temperature is above 5o C This function does not work when outside temperature is not above 5o C 2 Check tha...

Страница 25: ...The design and specifications are subject to change without prior notice for product improvement AlpineHomeAir com...

Отзывы: