User Manual
RacPower® BN52V-100-5.2k BP
2 Erica Way
Office:
+27 21 205 2000
Somerset West Business Park
Technical Support:
Somerset West, 7130
D.
INSTALLATION
1.
VOLTAGE-BASED INSTALLATION
The following values highlighted in blue must be set on the inverter/charger:
Parameter
Cell V
Value
Comment
V
high set
3.53 V
56.4 V
Typical bulk/absorption charge setpoint.
V
float
3.44 V
55.0 V
Floating voltage set point.
V
reconnect
3.06 V
49.0V
Mains or generator must reconnect to charge batteries.
V
low set
2.9 V
46.5V
Inverter must switch off the load.
•
Maximum Continuous Charge Current limit = 50 A
•
Recommended Charge Current = 10 A
•
Maximum discharge Current limit = 100 A
•
Recommended discharge current limit = 50 A
IMPORTANT: Inverter/charger voltage calibration
Some inverters/chargers have been known to return inaccurate results when measuring voltage.
In such cases, the inverter/charger should be calibrated as follows:
Compare the voltage values displayed by the inverter/charger with that of a calibrated voltmeter.
If the actual voltage differs by more than 100mV from that measured by the inverter/charger, apply this
difference to the highlighted values above (i.e. if actual voltage = 56V while inverter voltage = 56.5V,
the voltage difference = 0.5V should be subtracted from each of the set values above).
Note:
Some inverters/chargers have pre-programmed lead-acid related algorithms & functionalities such as
auto-
desulfation
and
equalisation
. These functionalities should be disabled, where possible.