42
Shenyang Bluelight Automatic Technology Co., Ltd.
BL6-DU20PX series Integrated Door Motor Controller User Manual
Hardware Handshake Output
Door Open Signal
Door Close Signal
Door Arrival to Open Limit
Door Arrival Close Limit
Hardware Handshake Input
Hardware Handshake Overtime
Over Load
Full Load
Half Load
Light Load
Safety Contact
Plate
Light Curtain
6.10
F9 Demonstration Running Parameters
Chart 6.10 F9 Demonstration Running Parameters
Function
Code
Name
Setting
Range
Factory
Default
Setting
Min
Unit
Description
F900
Demonstration
Delay
0~99s
5s
1s
This parameter is only valid in demonstration
running mode. It is the time interval between
torque holding stage after door arriving to
opening or closing limit and reverse to open or
close time. It should be set according to
practical situation.
F901
Demonstration
Automatic
Running
0~1
0
1
This parameter is used to set controller
whether starts to demonstration running in
demonstration running mode.
0: Disable the auto demonstration running.
As power on, an open or close instruction
starts the demonstration running.
1: Enable the auto demonstration running. As
power
on,
the
demonstration
running
automatically starts.