6.4
F3 Door-open Running Parameters
In speed control mode, all kinds of signals (travel switches) installation positions in door motor
system are shown in Figure 6.1.
Door Open
Limit Signal Door Open
Slowdown Signal
Door Close
Slowdown Signal
Door Close
Limit Signal
Door Open End Signal
Door Close End Signal
Open
Close
F
IGURE
6.1
S
PEED
C
ONTROL
S
WITCHES
I
NSTALLATION
D
IAGRAM
The Group F3 parameters and speed control related parameters should be set properly.
Slowdown switches and limit switches should be installed also. The door open running curve is
shown in Figure 6.2.
F303
F300
F305
Open Instruction
Slowdown Switch
Limit Switch
F301
F302
F304
F306
ON
ON
ON
OFF
OFF
OFF
F
IGURE
6.2
D
OOR
O
PEN
R
UNNING
C
URVE
D
IAGRAM
S
PEED
C
ONTROL
M
ODE
Door open process description in travel switch mode:
1. When the open instruction is valid, door motor raise the speed to the value of F300 in the
time F301 defined.
2. Low speed opening for F302, door motor raises the speed to a high speed defined by F303,
the raise time is F304.
3. Door open slowdown signal is valid, and the door motor slow down to the creep speed
defined by F305. The slowdown time is F306.