Blue Summit BPRPGE14 Скачать руководство пользователя страница 15

507295B03

Page 15  of  19

Issue 2122

To Shut Down Main Burners

1. 

Turn off electrical power to unit.

2.  Slide the gas valve switch to the “OFF” position (see 

Figure 7).

Post-Start Checklist

After the entire control circuit has been energized and the 
heating section is operating, make the following checks:

1.  Check for gas leaks, using soapy solution, in the unit 

piping as well as the supply piping.

2.  Check for correct manifold gas pressures (see Manifold 

Gas Pressure Adjustment Regulator sections).

3.  Check the supply gas pressure. It must be within the 

limits shown on the rating plate. Supply pressure 
should be checked with all gas appliances in the 

building at full fire. At no time should the standby gas 

pressure exceed 13” w.c., nor the operation pressure 
drop below 5” w.c. for natural gas units or 11” w.c. for 
propane gas. If gas pressure is outside these limits, 
contact the gas supplier for corrective action.

4. 

Adjust temperature rise to the range specified on the 

rating plate.

Manifold Gas Pressure Adjustment Regulator – Natural 
Gas

For purpose of input adjustment, the minimum permissible 
gas supply pressure is 5” w.c. for natural gas.

Gas input must never exceed the input capacity shown on 
the rating plate. 

The furnace is equipped for natural gas 

rated inputs with manifold pressure of 3.5” w.c.

The  manifold  pressure  can  be  measured  by  shutting  off 

the gas, removing the pipe plug in the downstream side 
of the gas valve, and connecting a water manometer 
or gauge. 

Under  no  circumstances  should  the  final 

manifold pressure vary more than 0.3” w.c. from the 

above specified pressures.

 To adjust the regulator, turn 

the adjusting screw on the regulator clockwise to increase 
pressure and input or counterclockwise to decrease 
pressure and input. See Figure 7 to assist in locating the 
regulator on the gas valve.

Check the furnace rate by observing the gas meter, making 

sure all other gas appliances are turned off. The test hand 

on the meter should be timed for at least one revolution, 
noting the number of seconds per revolution. The heating 
value of the gas can be obtained from the local utility.

BTU/HR 

Input

=

Cubic Feet per 

Revolution

x

3600

x

Heating 

Value

# Seconds per 

Revolution

For example, by actual measurement, it takes 38 seconds 
for the hand on the 1-cubic foot dial to make a revolution 
with a 100,000 BTU/HR furnace running. The result is 

99,750 BTU/HR, which is close to the 100,000 BTU/HR 
rating of the furnace.

Manifold Gas Pressure Adjustment Regulator – LP/
Propane Gas

LP/propane units require a LPG regulator on both the gas 
valve and on the LP/propane tank.

IMPORTANT

: For purpose of input adjustment, the 

minimum permissible gas supply pressure (inlet side of 
gas valve) is 11” w.c. for LP/propane.

If at any time ignition is slow and burner does not seem to 
be operating correctly, check manifold pressure (outlet side 
of the gas valve). 

It should be 10” to 10.5” w.c. pressure 

for LP/propane.

The furnace is designed to obtain rated input at 10” 
w.c. manifold pressure for propane.

High Altitude

The input rate shown on the rating plate is for elevations 
up to 2000 feet. For elevations from 2001 to 4500 feet, 
the input rate is reduced by 5%. For elevations above 
4500 feet, refer to the National Fuel Gas Code Z223.1 
(latest edition) or the Canadian Installation Codes CAN/
CGA-B149.1 & B149.2 for further details.

To check this pressure:

1.  Slide the gas valve switch to the “OFF” position (see 

Figure 7).

2.  Remove plug on valve marked “OUTLET PRESSURE.”

3.  Install a water manometer.

4.  Slide the gas valve switch to the “ON” position and 

initiate a call for heat. If manifold pressure must be 
adjusted, remove cap from pressure regulator and 
turn adjustment screw clockwise to increase pressure 
or counterclockwise to reduce pressure.

5. 

After  checking  pressure,  turn  gas  off,  remove 

manometer fitting, and replace pipe plug and regulator 

cap.

6.  Put furnace in operation and check plug for leaks 

using soapy solution.

Burner and Burner Orifice Instructions

To check or change burners or burner orifices:

1. 

Close the main manual gas shutoff valve and turn 

off all power to unit.

2.  Remove the burner access panel. 

3.  Disconnect the union in the gas supply line upstream 

of the gas valve and downstream of the manual shutoff 

valve.

4.  Label wires going to the gas valve, then disconnect 

the wires.

Содержание BPRPGE14

Страница 1: ...ON Table of Contents Unit Dimensions 2 Roof Curb Dimensions 4 Adjustable Roof Curb Dimensions 6 Installation 8 Venting 10 Duct System 11 Filters 11 Condensate Drain 12 Gas Piping 12 Electrical Wiring 13 Heating Start Up 14 Operation 16 Maintenance 17 If this unit is to be installed in a mobile or manufactured home application the duct system must be sized to achieve static pressures within the man...

Страница 2: ... 07 6 20 17 07 13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENTRY GAS ENTRY 6 94 2 33 11 49 16 07 18 52 3 25 4 56 20 31 21 06 23 19 RETURN AIR SUPPLY AIR TOP VIEW Unit Dimensions Small Base Gas Electric ...

Страница 3: ...LOW VOLTAGE ENTRY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49 2 39 2 33 11 49 16 07 18 52 6 94 3 25 10 06 19 49 SUPPLY AIR 25 81 26 56 28 68 11 49 2 33 47 66 56 13 Unit Dimensions Large Base Gas Electric ...

Страница 4: ...x 330 mm 44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 330 3 76 NOTE If bottom entry is used condensate from the heat exchanger may leak during warm ambient temperatures in humid climates Ensure that bottom entry is watertight if used Roof Curb Dim...

Страница 5: ...ase 3 x 13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bottom entry is used condensate from the heat exchanger may leak during warm ambient temperatures in humid climates Ensure that bottom entry is watertight if used Roof Curb Dimensions Large Base...

Страница 6: ...8 2 1 8 14 1 3 1 2 13 1 2 44 3 8 Bottom Curb Assembly Opening for Gas Entry thru base 11 5 8 5 1 2 5 3 4 3 5 8 1 3 8 17 1 4 13 7 8 16 7 8 44 3 8 Insulated Panels Opening for Power Line Entry thru base NOTE Roof deck may be omitted within confines of curb NOTE If bottom entry is used condensate from the heat exchanger may leak during warm ambient temperatures in humid climates Ensure that bottom en...

Страница 7: ...8 11 5 8 2 1 8 19 3 8 11 5 8 14 23 1 8 1 5 1 2 5 3 4 3 1 2 3 1 2 13 1 2 6 7 8 52 7 8 44 3 8 Insulated Panels Opening for Power Line Entry thru base Bottom Curb Assembly Opening for Gas Entry thru base NOTE Roof deck may be omitted within confines of curb NOTE If bottom entry is used condensate from the heat exchanger may leak during warm ambient temperatures in humid climates Ensure that bottom en...

Страница 8: ...ght bill A separate request for inspection by the carrier s agent should be made in writing Location Use the following guidelines to select a suitable location for these units 1 Unit is designed for outdoor installation only Unit must be installed so all electrical components are protected from water 2 Condenser coils must have an unlimited supply of air 3 For ground level installation use a level...

Страница 9: ...rubs to obstruct condenser air discharge outlet combustion air inlet or vent outlet Clearance to Combustibles Clearance for Service Access Front of unit 0 in 24 in Back of unit 0 in 0 in Left side 0 in 24 in Right side from vent hood 12 in 24 in Base of unit 0 in 0 in Top of unit 0 in 48 in Minimum clearance to combustible material below the flue is 10 inches to allow proper dissipation of flue ga...

Страница 10: ...t hood inside the control compartment Locate the vent hood and attach to side of utility panel with screws provided in the instruction bag see Figure 2 Vent Hood Attach with Screws Figure 2 Installing the Vent Cover 2 All panels must be in place for rigging 3 Place field provided spreaders in place Spreaders must be of adequate strength and length must exceed unit dimension by 6 inches Units may a...

Страница 11: ...el Gas Code ANSI Z223 1 latest edition or CAN CGA B149 1 2 Canadian Installation Codes to correct improper operation of common venting system Duct System The duct system should be designed and sized according to the methods in the Air Conditioning Contractors of America ACCA manual that is most appropriate to the installation application A closed return air duct system shall be used This shall not...

Страница 12: ...lled immediately upstream of the gas supply connection to the furnace Gas Connection The gas supply line is routed through the gas entry location on the side of the unit see Figure 4 A grommet is provided in the instruction bag and should be used to seal gas supply line to gas entry of control compartment Table 2 Unit Air Filter Sizes inches Unit Model Filter 1 Filter 2 24 30 36 14 x 20 x 1 20 x 2...

Страница 13: ...est edition Canadian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C minimum Run the 208 or 230 volt 60 hertz electric power supply through a fused disconnect switch to the control box of the unit and connect as shown in the wiring diagram located on the inside of the control access panel Power supply to the unit mu...

Страница 14: ...connect the thermostat to the unit Heating Start Up For Your Safety Read Before Lighting Furnace is equipped with a direct ignition control Do not attempt to manually light the burners CAUTION Pre Start Checklist Complete the following checks before starting the unit 1 Check the type of gas being supplied Be sure it is the same as listed on the unit nameplate 2 Make sure that the vent cover has be...

Страница 15: ...ing value of the gas can be obtained from the local utility BTU HR Input Cubic Feet per Revolution x 3600 x Heating Value Seconds per Revolution For example by actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with a 100 000 BTU HR furnace running The result is 99 750 BTU HR which is close to the 100 000 BTU HR rating of the furnace Manifold Gas Pres...

Страница 16: ...r system components Continuous Fan With the proper thermostat and sub base continuous blower operation is possible by closing the R to G circuit Cooling blower delay is also functional in this mode 5 To change orifice a Remove screws that fasten the manifold to the burner box assembly and remove the manifold b Remove the orifices then install replacement orifices c To reassemble Reverse above step...

Страница 17: ... condition caused by inadequate airflow occurs This closes the main gas valve Pressure Switch If the combustion air blower should fail the pressure switch prevents the spark electrode and gas valve from being energized Maintenance Periodic inspection and maintenance normally consists of changing or cleaning the filters and cleaning the evaporator coil On occasion other components of the furnace ma...

Страница 18: ... the reverse order they were removed in Steps 1 through 3 10 When replacing the flue collector box be careful so as not to tear the adjoining insulation 11 Assure that all joints on the vent side of the combustion system are air tight Apply a high temperature 500 F sealing compound where needed Control System Diagnostics Table 4 Fault Codes LED Status Flashing Rate Fault Description Slow Flash One...

Страница 19: ...507295B03 Page 19 of 19 Issue 2122 Figure 8 Wiring Diagram Single Phase CT ...

Отзывы: