507276-04B
Page 21 of 56
Issue 1904
Maximum Allowable Exhaust Vent Lengths with Furnace Installed in a Closet or Basement Using Ventilated Attic or Crawl
Space for Intake Air in Feet
Standard Termination at Elevation 0 - 4,500 ft
Number of
90° Elbows
Used
2" Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
1
66
51
29
9
95
95
73
38
113
112
93
93
2
61
46
24
4
90
90
68
33
108
107
88
88
3
56
41
19
n/a
85
85
63
28
103
102
83
83
4
51
36
14
80
80
58
23
98
97
78
78
5
46
31
9
85
75
53
18
93
92
73
73
6
41
26
4
70
70
48
13
88
87
68
68
7
36
21
n/a
65
65
43
8
83
82
63
63
8
31
16
60
60
38
3
78
77
58
58
9
26
11
55
55
33
n/a
73
72
53
53
10
21
6
50
50
28
68
67
48
48
Standard Termination Elevation 4,501 - 10,000 ft.
Number of
90° Elbows
Used
2" Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
1
66
51
29
n/a
95
95
73
38
113
112
93
93
2
61
46
24
90
90
68
33
108
107
88
88
3
56
41
19
85
85
63
28
103
102
83
83
4
51
36
14
80
80
58
23
98
97
78
78
5
46
31
9
85
85
53
18
93
92
73
73
6
41
26
4
70
70
48
13
88
87
68
68
7
36
21
n/a
65
65
43
8
83
82
63
63
8
31
16
60
60
38
3
78
77
58
58
9
26
11
55
55
33
n/a
73
72
53
53
10
21
6
50
50
28
68
67
48
48
* Size intake and exhaust pipe length separately. Values in table are for intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
* Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
Table 5C.
Содержание BG951UHE
Страница 3: ...507276 04B Page 3 of 56 Issue 1904 Figure 1 Parts Arrangement ...
Страница 22: ...507276 04B Page 22 of 56 Issue 1904 Figure 25 Figure 26 ...
Страница 37: ...507276 04B Page 37 of 56 Issue 1904 Figure 59 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Страница 43: ...507276 04B Page 43 of 56 Issue 1904 Figure 67 Typical Wiring Diagram ...