21
Model BD306 Dual-Input Pump Controller Instruction Manual
6.4.12. Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other
devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the
return. This power supply is capable of sourcing up to 40 mA.
6.4.13. External Relays & Digital I/O Connections
The relay and the digital I/O expansion modules BDXM & BDIO are connected to the meter
using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion
modules are identical and interchangeable; they are used to connect additional modules to the
system.
Note: The jumper located between the RJ45 connectors of the BDIO must be removed on the
second digital I/O module in order for the system to recognize it as module #2.
WARNING!
Do not connect or disconnect the expansion modules with
the power on!
More detailed instructions are provided each optional
expansion module.
Return to Table of Contents