Connect DC Power source 

for input, turn on the power 

switch and the machine 

does not respond 

1.

 

The input DC voltage does not 

meet  the  requirements  or  is 

too lower 

2.

 

The input polarity is reversed. 

1.

 

Check if the DC input voltage is too lower can 

not meets the requirements 

2.

 

Check if input polarity is reversed. 

Customer's DC input circuit 

breaker can not be switch 

and close 

1.

 

Select  the  bigger  capacity 

circuit breaker 

2.

 

Inverter  internal  circuit  failure 

causes  the  machine  to  short 

circuit 

1.

 

Select the bigger capacity circuit breaker 

2.

 

Switch  on  the  DC  circuit  breaker  then  Switch 

on the AC circuit breaker 

3.

 

If it still did not work mean the inverter internal 

circuit are broken or short circuit 

Can not switch the dc and 

bypass in automatic 

1.

 

AC 

Mains 

voltage 

and 

frequency  exceed  the  Inverter 

input limited range: 

2.

 

The dial switch (DIP Switch)on 

the  rear  panel  is  set  to  the 

wrong position. 

1.

 

Check  whether  the  ac  mains  voltage  and 

frequency  exceed  the  input  range  of  the 

inverter 

2.

 

Check  whether  the  dial  switch (DIP  Switch)  in 

the corresponding position or not 

10 

For other fault be happen , please contact with factory after sale service support team. 

 

PART 13.Maintenance   

1.

 

In order to ensure continuous normal operation of the inverter, regular maintenance and maintenance are required. 

2.

 

The  installation  and  storage  of  inverter  should  avoid  high  corrosive,  high  dust,  high  temperature  and  high  humidity 

environments as much as possible. 

3.

 

Avoid metal material falling into the box. 

4.

 

Periodically check whether the connection line is aging and the cable connection point is tight and safe or not . 

5.

 

Clean the cooling fan regularly and check if the fan is normal. 

 

Содержание OPT-R 110V Series

Страница 1: ...ual Tel 0086 023 67628702 Email tech cqbluejay com www cqbluejay com Add Block 3A 13 25 No 153 Jingyu Avenue Jiangbei Qu Chongqing City 401147 OPT R 0 5KVA 10KVAPure Sine Wave Inverter User Manual 19 Rack mount ...

Страница 2: ...ther electrical equipment To prepare for the instability of the city electricity and power cuts It also prevents various distortions of utility power such as power supply voltage drop surge voltage spike voltage and broadcast frequency interference PART 2 Customized Range Input Output voltage Capacity 19Inch 1U 2U 4U Rack Mount With LCD LED Display With RS232 Communication port Power Factor 0 8 Wi...

Страница 3: ...t voltage and frequency 220Vac 50Hz Rate output current A 1 8 3 6 7 2 10 8 14 5 18 2 21 8 29 36 3 Output voltage accuracy V 220 3 Output frequency accuracy Hz 50 0 1 Waveform distortion rate THD 3 Linear load Dynamic Response 5 Load 25 100 Power Factor PF 0 8 Over load ability 100 125 10mins 125 150 15seconds 150 shut down Immediately Efficiency 85 80 Resistive load Bypass conversion time ms 5ms O...

Страница 4: ...6 6 2 KVA 8 3 2 KVA 7 8 3 KVA 117 3 KVA 57 3 KVA 24 9 3 KVA 12 4 3 KVA 11 7 4 KVA 77 4 KVA 33 4 4 KVA 16 7 4 KVA 15 6 5 KVA 98 5 KVA 36 6 5 KVA 18 3 5 KVA 19 6 6 KVA 117 6 KVA 51 3 6 KVA 22 6 KVA 23 5 8 KVA 156 8 KVA 68 8 KVA 34 2 8 KVA 34 2 10 KVA 196 10 KVA 85 10 KVA 42 7 10 KVA 39 Remarks 1 Due to the difference in the instrument used during the test the range points may be slightly deviated 2 ...

Страница 5: ...hree pages on the LCD screen and each page shows two lines of content First page Output voltage XXX X Vac Load ratio XXX Second page DC input XXX X Vdc AC input XXX X Vac Third page Load power XX XX kW Output frequency XX X Hz 3 BLA Backlight button Press the backlight key BLA the backlight is on 4 LIN AC City Power indicator The LIN Indicator ON Mean the inverter work in AC input and ac output in...

Страница 6: ...eck the packing of the goods when receiving the goods that the goods company is carrying In case of any damage please indicate on the receipt Storage Keep it in a cool dry ventilated place away from highly corrosive dusty hot and humid environments If you do not use the inverter for a long period of time you should be able to use it every 6months Check the machine nameplate Check if the specificat...

Страница 7: ...023 67628702 Email tech cqbluejay com www cqbluejay com Add Block 3A 13 25 No 153 Jingyu Avenue Jiangbei Qu Chongqing City 401147 PART 8 Appearance Dimension 19inch 1U Rack Mount Front Rear View 500VA 2000VA Front Rear View ...

Страница 8: ...ser Manual Tel 0086 023 67628702 Email tech cqbluejay com www cqbluejay com Add Block 3A 13 25 No 153 Jingyu Avenue Jiangbei Qu Chongqing City 401147 3KVA 6KVA Front Rear View 8KVA 10KVA Front Rear View ...

Страница 9: ... 023 67628702 Email tech cqbluejay com www cqbluejay com Add Block 3A 13 25 No 153 Jingyu Avenue Jiangbei Qu Chongqing City 401147 PART 9 Wiring diagram description 1U Rack Mount type 2U Rack Mount type 4U Rack Mount type ...

Страница 10: ... the inverter after switch DIP switch if not it did not work Switch the DIP switch to the digital side is 1 Switch the DIP switch to the NO side is 0 0000 1111 Noted Connect the inverter with the Earth is necessary to make sure it can safety and normal operation of the inverter and reduce electromagnetic interference The grounding wire must be grounded GND and the earth grounding terminal should b...

Страница 11: ... following figure for proper handling Item Fault Possible Reason Solutions 1 Battery load over temperature LED 1s 1 flash Turn off the output due to internal overheating 1 Check the fan is running or not 2 Check the air vents are blocked or not 3 The environment temperature is too high or not 4 Reduce the load 5 Wait 10 minutes for inverter cooling and drop of the temperature then restart 2 The lo...

Страница 12: ...r internal circuit are broken or short circuit 9 Can not switch the dc and bypass in automatic 1 AC Mains voltage and frequency exceed the Inverter input limited range 2 The dial switch DIP Switch on the rear panel is set to the wrong position 1 Check whether the ac mains voltage and frequency exceed the input range of the inverter 2 Check whether the dial switch DIP Switch in the corresponding po...

Отзывы: