Temperature & Humidity Controller

 

 
 

BJ-S-W2S2-K2

 

 
 

User Manual

 

 
 
 
 

Version

1.4

 

 
 
 

 

 

Содержание BJ-S-W2S2-K2

Страница 1: ...l 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing Temperature Humidity Controller BJ S W2S2 K2 User Manual Version 1 4 ...

Страница 2: ...Temperature Humidity controller and help to solve the various problems at the scene 1 Before the meter turning on the power supply be sure that the power supply within the provisions of the instrument 2 When installation the current input terminal must non open voltage input terminals must Non short circuit 3 Communication terminal RS232 or RS485 is strictly prohibited to impose high pressure 4 Be...

Страница 3: ...636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing Directory CONTENTS Page 1 SUMMARIZE 1 2 FEATURES 1 3 SPECIFICATIONS 2 4 INSTALLATION 3 5 OPERATION MODE 5 6 SETUP PROCEDURE 6 7 SAFETY CONSIDERATIONS 8 8 MAINTENANCE 8 9 TECHNICAL SERVICE 8 ...

Страница 4: ... with various output types allowing different systems to reach a stable control status very quickly can be used in the worst environment for long term use applied to the various occasion which need temperature and humidity control It is the ideal product to protect the normal efficient operation of power equipment and to reduce cost And can be used in other place need of temperature and humidity c...

Страница 5: ... Humidity 1 98 RH Hum sensor accuracy 3 0 RH Cable length 2 m 3m option Sampling rate 400 msec per scan Display Display method 2 line x 3 character 7 segment LED display Keypads Menu Enter increase decrease Control output Relay output 2 route 250VAC 5A 1PH resistive load or passive node depends on client requirement RS 485 communication MODBUS ASCII RTU communication protocol Ambient condition Pro...

Страница 6: ...onnections keep inside the cabinet 1 Insert the controller through the panel cutout 2 Insert the mounting bracket into the mounting groove at the top and bottom of the controller and push the mounting bracket forward until the bracket stops at panel wall 3 Completion status Notes 1 The controller must not be power on until this is completely installed 2 Panels shall not exceed 12 mm maximum thickn...

Страница 7: ...er 1 Place socket to a position on the DIN rail expand the fixed buckle and wiring 2 Insert the controller to the bracket forward until stops at the end Pins will make the controller installed in the correct direction 3 Turn the buckle down to the fixed hole Notes 1 Socket are of the points please sure that the interface 1 2 7 8 is at the upwards 2 Mounting holes with pins if you can not successfu...

Страница 8: ...available screens Notes If there is any sensor off line the display will show to indicate the sensor failure Up key Press this key to increase values displayed on the display Hold down this key to speed up the incremental action Down key Press this key to decrease values displayed on the display Hold down this key to speed up the decrements Menu key Pressing the Manu key the can open the programmi...

Страница 9: ...to be entered in case that this password is not correct will not be set on the meter At normal display mode press to enter the programming mode meter display then press Controller display Ask for the password Press and to increase or decrease the number to switch password After password switch press to confirm the input If password is correct meter can enter next setting Temperature control value ...

Страница 10: ...s value will act contactor 2 K2 Probe 2 Temperature alarm value When probe 2 detect temp raise decline this value will act contactor 1 K1 Probe 2 Hysteresis value After probe 1 over the trig value will reverse down the value can release contact action Probe 2 Temperature trig value When probe 2 detect temp raise decline this value will act contactor 2 K2 Control mode 0 for Rising edge control 1 fo...

Страница 11: ...enance No adjustment maintenance or repairing action should be done when the instrument is open and powered on should those actions are essential high qualified operators must perform them Before any adjustment replacement maintenance or repairing operation is carried out the controller must be disconnected from any power supply source When any protection failure is suspected to exist the controll...