5. TECHNICAL DATA
Technical data
Unit of measure
FARMER 47 kW
Nominal heating capacity water 90/70°C and inlet air
temperature 0°C.
kW
46,8
Heating power range.
kW
20-47
Maximum airflow.
m3/h
4400
Maximum range of air stream.
m
10-25
Number of rows in heater.
number
2
Weight including water/ without water.
kg
29/27
Capacity of water.
dm3
2,0
Air temperature rise. *
°C
29,6
Maximum temperature of heating agent.
°C
110
Maximum operating pressure.
MPa
1,6
Rated current.
A
0,82
Power supply voltage.
V/Hz
230/50
Motor power
W
180
Motor speed
rev/min
1380
Motor IP
-
54
Ferrules diameter
„
3/4
Dimensions (height/depth/width)
mm
660/696/384
Technical data of Blowair Farmer 47 kW:
Parameters
Farmer 47 kW
Inlet and outlet water temperature[°C]
90/70
Inlet air temperature [°C]
-20
-10
0
10
Heating capacity [kW]
61,9
54,2
46,8
39,7
Outlet air temperature [°C]
16,2
23,0
29,6
36,0
Water flow[m³/h]
2,73
2,39
2,06
1,75
Pressure drop in the heat exchanger [kP]
24
19
14
11
Parameters
Farmer 47 kW
Inlet and outlet water temperature[°C]
80/60
Inlet air temperature [°C]
-20
-10
0
10
Heating capacity [kW]
55,0
47,4
40,2
33,3
Outlet air temperature [°C]
12,2
18,9
25,4
31,8
Water flow[m³/h]
2,42
2,08
1,77
1,46
Pressure drop in the heat exchanger [kP]
20
15
11
8
Parameters
Farmer 47 kW
Inlet and outlet water temperature[°C]
70/50
Inlet air temperature [°C]
-20
-10
0
10
Heating capacity [kW]
48,1
40,7
33,7
26,9
Outlet air temperature [°C]
8,2
14,8
21,3
27,6
Water flow[m³/h]
2,1
1,78
1,47
1,18
Pressure drop in the heat exchanger [kP]
16
11
8
5
Parameters
Farmer 47 kW
Inlet and outlet water temperature[°C]
50/30
Inlet air temperature [°C]
-20
-10
0
10
Heating capacity [kW]
34,2
27,1
20,4
13,9
Outlet air temperature [°C]
0,0
6,5
12,9
19,1
Water flow[m³/h]
1,48
1,18
0,88
0,6
Pressure drop in the heat exchanger [kP]
9
6
3
2
6. 3 ASSEMBLY
Blowair Farmer devices can be assembled on the
wall or ceiling via holders or rotational holder,
which are additional elements. The drawings be-
low show the ways of assembly. In the bigger ac-
commodation it is recommended to assemble
more than one device. Follow the parameters
which are provided on the drawings.
Drawing 2. Assembly on the ceiling.
Drawing 3. Assembly on the wall.
Drawing 4. Example arrangement for few devices
in the room.
Drawing 5. Three versions of the assembly position
while using the holders.
Blowair devices can be assembled on the wall or
ceiling via holders or rotational holder, which are
additional elements. It is possible to assemble the
device in parallel on the angle 60° and 45°.
7. INSTALLATION INSTRUCTIONS.
The installation should be made by the qualified
stuff, who possess the needed rights to install elec-
trical devices, as instructed in the following docu-
mentation. To install the air waiter heaters Blowair
Farmer 47 kW use the duct size 2 x 2,5mm².
8. PRECAUTIONS & WARNINGS
t
All works concerning electrical installation
should be made by the qualified stuff, who
possess the qualifications due to the domes-
tic and local norms. These recommendations
include service and disassembly as well. Not
following to the recommendations may
cause electrocution, device damages or its
incorrect work.
t
Before service or exchange of the device it is
obligatory to cut off the current supply.
t
Do not cover the inlet and outlet of the device.
t
Do not use the device in room with high
moisture or close to the water basin.
t
Do not install, service the device with wet
hands or barefoot.
*Temperature rise according to parameters: water 90/70°C and inlet air temperature 0°C.