Set the LUX knob clockwise until the SUN symbol is reached, then turn the SENS knob clockwise until it reaches de 

+ symbol, and for last turn the TIME knob anti-clockwise until the 10s symbol is reached.

The next step is to switch on the power, is everything is as mentioned above, the light will turn on imidiatly and after 

10s +- 3 seconds the light should turn off. 

The next time the Square Sense receives a signal it will work as normally. Once it receives the second signal the timer 

starts fresh,  which means that the lamp time will star from the beginning.

Turn the LUX anti-clockwise to the minimum (3). if the ambient light is less than 3 Lux (darkness) the lamp will turn 

on.

V. Test

No Power:

Resolution: 

Check the load

                      Check if the indicator is turn on after the detection signal is sent? If so please check the load, if it is not turned 

                      on, please check the Lux setting is correct.

Poor Sensitivity:

Resolution: 

Make sure there’s no objects that may obstruct. If the problem still remains check the heigh and the source of 

                       the detection is in the detection field.

Can’t turn off the load:

Resolution:

 Check and see there’s an continuous signal. The timer is set on max. 

VI. Troubleshooting

EU Reg nº 003469376

www.blink.com.pt

All responsabilities for defects or damages are hereby rejected if caused by: incorrect assembling

of the product, incorrect supply, use of lamps not suitable for this product, external agents. BLI/209.EN