7 TARGET COS PHI
: By setting the target cos phi, the power factor to
be attained via the PF correction is defined. It is also set via the
é
/
ê
keys. The range may be selected from 0.3 inductive to 0.3
capacitive. Confirming and saving the value with ENTER leads to
the next point.
8 CONNECTING TIME
: This refers to the time between connecting
the capacitors to increase the momentary network capacitance. It
should be noted that in practical operation the real connection time
is affected by the discharge time (locking time).
Setting range:
1 ...255 sec.
Default setting:
40 sec.
Selection is performed via the
é
/
ê
keys. Continue with ENTER
9
DISCONNECTING TIME
: This refers to the time between
disconnecting the capacitors to reduce the momentary network
capacitance.
Setting range:
1 ...255 sec.
Default setting:
40 sec.
Selection is performed via the
é
/
ê
keys. Continue with ENTER
10
DISCHARGE TIME
: This is the time for which an individual output
is blocked between connecting and disconnecting. This blocking
time has priority over connecting and disconnecting times. It
depends on the capacitor discharge rating and thus is specified by
the compensation network. The discharge time of a conventional
network without additional fast-discharge resistors or chokes
should be set to no less than 40 seconds.
For setting of a second discharge time see 'Expert Mode' point 10
Setting range:
1 ...255 sec .
Default setting:
60 sec.
Selection is performed via the
é
/
ê
keys. Continue with ENTER
- 11 -