Software Setup
78
ER41, ER24
Cmd Register
Bit Mapping of the Control Word
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Fault reset
Reserved
(=0)
Reserved
(=0)
Reserved
(=0)
Enable
operation
Quick stop
Enable
voltage
Switch on
0 to 1
transition =
Error is
reset (after
cause of
error is no
longer
active)
1 = Run
command
0 = Quick
stop active
Authorization
to supply AC
power
Mains
contactor
control
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Manufacturer
specific
assignable
Manufacturer
specific
assignable
Manufacturer
specific
assignable
Manufacturer
specific
assignable
Manufacturer
specific
Reserved
(=0)
Reserved
(=0)
Halt
0 = Forward
direction
asked
1= Reverse
direction
asked
Halt
Command
State
Transition
Final
Operating
State
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Example
Value
Fault
Reset
Enable
Operation
Quick
Stop
Enable
Voltage
Switch
On
Shutdown
2, 6, 8
3 - Ready
to switch
on
X
X
1
1
0
0006 hex
Switch on
3
4 -
Switched
on
X
X
1
1
1
0007 hex
Enable
operation
4
5 -
Operation
enabled
X
1
1
1
1
000F hex
Disable
operation
5
4 -
Switched
on
X
0
1
1
1
0007 hex
Disable
voltage
7, 9, 10, 12
2 - Switch
on
disabled
X
X
X
0
X
0000 hex
Quick stop
11
6 - Quick
stop
active
X
X
0
1
X
0002 hex
7, 10
2 - Switch
on
disabled
Fault
reset
15
2 - Switch
on
disabled
0 [gs56] 1
X
X
X
X
0080 hex
X: Value is of no significance for this command.
0[gs56] 1: Command on rising edge.
Содержание ER41
Страница 1: ...ER41 ER24 PROFINET Manual 08 2017 www blemo com ...
Страница 8: ...8 ER41 ER24 ...
Страница 14: ...Presentation 14 ER41 ER24 ...
Страница 30: ...Basics 30 ER41 ER24 ...
Страница 102: ...Software Setup 102 ER41 ER24 ...
Страница 103: ...Software Setup 103 ER41 ER24 ...
Страница 104: ...Software Setup 104 ER41 ER24 ...
Страница 112: ...Operation 112 ER41 ER24 ...
Страница 125: ......
Страница 126: ......