9
To facilitate ease-of-access to the fan’s power supply, the lower right corner of the front
cladding (as shown below – location relative to facia) will need to be notched so that the
extension cord can be fed through the wall. It is recommended that the notch is no greater
than 50x50mm so that the facia covers the entire hole.
POWER SUPPLY FOR FAN
Provide a power point in the cavity under the heater for connecting the fan in the heater. If
the cavity under the heater will not be accessible once the heater is installed (such as
through a removable vent) then ensure an extension cord long enough to reach out of the
front of the opening is lying in the base of the cavity. When connecting the lead from the fan
to the extension cord, it is suggested to tape the connection in the event that if the fan may
require removal and the lead has to be pulled through the 50x50mm notch.
FLUE REQUIREMENTS
Install a 150mm diameter double cased flue kit to comply with AS 2918. The double casing
must extend from the top of the zero clearance box all the way through to the top where the
flue terminates. A hole of 300 mm diameter is required in the ceiling with a minimum 25 mm
clearance between any combustible material and the 250 mm outer casing.
50x50mm notch