MOUNTING AND SET-UP
READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.
WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT
MAINTENANCE AND REPAIR.
HUMIDITY SENSOR MOUNTING
The humidity sensor is not included in the delivery set and can be ordered separately.
The humidity sensor must be installed prior to unit mounting.
Unit mounting sequence:
• Remove the mounting screws of the service side panel of the unit and take it off.
• Install the humidity sensor into the mount from the side of the extract air duct and connect the humidity sensor connector to the
respective connector coming from the control unit, refer to the External wiring diagram.
• Install the sensor cover back.
Washer
Nut
Threaded rod
Vibration absorbing rubber
min 20 mm
UNIT MOUNTING
The unit is designed for ceiling mounting with anchor threaded bolts, nuts and vibration-absorbing rubber.
Fasteners for unit mounting are not included in the delivery set and should be ordered separately.
While choosing fasteners consider the material of the mounting surface as well as the weigh of the unit, refer to the Technical Data
section. Fasteners for unit mounting should be selected by the service technician.
Before mounting make sure that the casing is free of any foreign objects like film or paper.
While installing the unit ensure convenient access for subsequent maintenance and repair.
Minimum required distance from the unit to the ceiling is at least 20 mm.
To attain the best performance of the unit and to minimise turbulence-induced air pressure losses, connect the straight air duct section
to the spigots on both sides of the unit while mounting.
Minimum straight air duct length:
• equal to 1 air duct diameter on intake side
• equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects.
To prevent uncontrollable access to the fans the spigots may be covered with a protecting grille or other protecting device with mesh
width not more than 12.5 mm.