www.blaubergventilatoren.de

8

HRV/ERV H 120(170) 

SET THE THREE-POSITION SWITCH INTO THE STAND BY POSITION 

TO ACTIVATE THE REMOTE CONTROL. 

3. Humidistat. 

The humidistat is used for indoor humidity control.  When indoor humidity level rises above the set point, the unit changes into the High Speed Mode and 

runs with the high speed until the humidity level falls down below the set point. The humidity set point is adjustable.    

4. Remote mechanical timer. 

In case of the timer activation the unit changes into the High Speed Mode. 

5. Switch. 

In case of the switch contact closing the unit changes into High Speed Mode and reverts to permanent Low Speed Mode when the switch contacts are 

opened.

SERVICING AND MAINTENANCE

Servicing of the unit  is required 3-4 times per year. Besides general cleaning, the following operations are required: 
1. Filter maintenance (3-4 times per year)
Dirty filters increase air resistance in the system and reduce supply air flow to the premises.  

 

Clean or replace the filters as often as required, but at least 3-4 times per year. Clean the filter with running  water or a vacuum cleaner.

 

 After two cleaning replace the filter. Contact your local supplier for new filters. 

2. Heat recovery core  maintenance (once per year). 
Some dust can get accumulated on the heat recovery core block even if you clean or replace the filters regularly in compliance with above procedure. To 
maintain the high heat exchange efficiency, pull out and clean the heat recovery core  with warm detergent solution. Re-install the dry heat recovery  to 
the unit. 
    3.  

Fan maintenance (once per year). 

 

Even if you perform regular maintenance of the filters and the heat recovery core, some dust and grease can get accumulated inside the fans and 

reduce the fan performance and supply air flow. 
 

Clean the fans with a soft brush or dry cloth. No water and abrasive detergent, sharp objects or solvents are allowed for cleaning to prevent the 

impeller damage. 

4. 

Condensate drainage system maintenance (once per year), (applicable only for HRV H 120(170).

 

The drain hose can get clogged with the extracted particles. Clean the drain hose is required. Check proper functioning of the drain system by 

pouring some water into the drain pan at the unit bottom. Clean the U-trap and the drain tubes if required. 

5. 

Supply air flow inspection (twice per year).

 

Leaves and other objects can clog the intake grille and decrease  the unit performance and supply air flow. Check the intake grille twice per year 

and clean it if required. 

6. 

Air ductwork maintenance (once in 5 years).

 

Even if you fulfill all the above maintenance guidelines regularly, a certain amount of dust is accumulated inside air ducts. That reduces the 

ventilation system performance. Clean or replace the air ducts periodically. 

TROUBLESHOOTING

Problem 

Possible reasons 

Solving 

The fan(s) do(es) 

not start running. 

Power supply is off.

Make sure the power supply line is connected correct, otherwise troubleshoot the 

connection error. 

Thermal fuse is melted. 

Disconnect the unit from power mains. Remove the overload. Replace the thermal fuse 

and check the unit. 

Cold supply air.

The extract filter is clogged. 

Clean or replace the extract filter.

The heat recovery core is 

frozen. 

Check the heat recovery core condition. Shutdown the unit and turn it on after the 

freezing danger is no longer imminent.  Check the thermostat setpoints. 

Low air capacity.

Too low set rotation speed.

Check the speed control settings.

The filters, fans or heat recovery 

core are clogged. 

Clean or replace the extract filters; clean the fans and the heat recovery core. 

The ventilation system is 

clogged or damaged. 

Check the diffusers and louvre gravity shutters opening, check the  exhaust hood and 

intake grille and clean those if required; make sure that the air ducts are not clogged or 

damaged. 

Noise, vibration.

The impeller(s) is (are) clogged. Clean the fan impeller(s). 
Fan screw tightening is loose.

Check and tighten the screws if required. 

Water leakage.

The drain system  is clogged, 

damaged or wrong arranged.

Clean the drain pipe is required. Check the drain pipe slope, U-trap and temperature 

conditions. 

Содержание ERV H 120

Страница 1: ...OPERATION MANUAL EN HRV H 120 ERV H 120 HRV H 170 ERV H 170 HEAT RECOVERY VENTILATOR ...

Страница 2: ...rranty 9 The HRV ERV H 120 170 unit is designed for ceiling mounting The HRV ERV H 120 170 is designed for ceiling and wall mounting The unit is designed to save thermal energy by means of heat recovery and is one of the energy saving components used in the buildings and premises The ventilator is a component unit and is not designed for independent operation The unit is designed to provide perman...

Страница 3: ...se 1 pce Oil filter 1 pce Packing box 1 pce The unit is designed for indoor installation and operation at the ambient air temperature ranging from 34 F 1 С up to 122 F 50 С Ingress Protection rating IP44 for the unit motors IP 22 for the assembled unit connected to air ducts The unit net weight is 66 lbs 30 kg The unit series designation basic overall and connecting dimensions are shown in fig 1 T...

Страница 4: ...RYERS OR SIMILAR EQUIPMENT TO THE VENTILATION SYSTEM DO NOT OPERATE THE UNIT IN THE AIR AND DUST MIXTURE ENVIRONMENT STRUCTURE AND OPERATING LOGIC Fig 2 Unit structure and operating logic The unit has the following operating logic fig 2 Warm stale extract air from the room flows through the air ducts to the unit is purified in the extract filter and is supplied to the heat recovery core and exhaus...

Страница 5: ...Frost protection thermostat MOUNTING AND SET UP Fig 3 Unit mounting While mounting the unit provide enough access for the unit maintenance and servicing Mount the unit to ceiling with threaded rods fixed inside the dowels attached to the ceiling or by means of the belts that are rigidly fixed to horizontal plane fig 3 The unit can be installed on mounting supports with adjustable height for connec...

Страница 6: ...drain system and provide air heating min 3 1 3 5 2 4 fig 5 Condensate drainage The unit is designed for connection to single phase ac 120 V 60 Hz power mains The unit is equipped with a power cable and a plug and can be connected to any standard grounded outlet The power cable is connected to the terminal X1 by default Connect the unit to power mains through the external automatic switch integrate...

Страница 7: ...sition speed switch that enables low speed modes Low as well as Med and Stand by mode which enables total air quality control fig 7 Up to five external control devices may be connected to the terminals 2 11 fig 7 that turn the unit to high speed ventilation in case of activation of any of the control devices Three speed switch Terminals for connection of the remote control panel Fig 7 Unit control...

Страница 8: ...te drainage system maintenance once per year applicable only for HRV H 120 170 The drain hose can get clogged with the extracted particles Clean the drain hose is required Check proper functioning of the drain system by pouring some water into the drain pan at the unit bottom Clean the U trap and the drain tubes if required 5 Supply air flow inspection twice per year Leaves and other objects can c...

Страница 9: ... replacement or repair of the unit components or a specific part of such unit component The warranty repair does not include routine technical maintenance unit installation dismantling unit setup To benefit from warranty repair the user must provide the unit the user s manual with the purchase date stamp and the payment paperwork certifying the purchase The unit model must comply with the one stat...

Страница 10: ...pany Stamp The single room reversible energy regeneration ventilator HRV ERV H 120 170 has been connected to power mains pursuant to the requirements stated in the present user s manual Company Name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all applicable local and national construction elec...

Страница 11: ...11 www blaubergventilatoren de HRV ERV H 120 170 ...

Страница 12: ...www blaubergventilatoren de HRV ERV_H_120 170 _EN 01 ...

Отзывы: