BLAUBERG Axis-Jet Series Скачать руководство пользователя страница 1

Jet axial fan

USER’S MANUAL 

EN

axis-Jet

Содержание Axis-Jet Series

Страница 1: ...Jet axial fan USER S MANUAL EN Axis Jet ...

Страница 2: ...urned over to the receiving operator This user s manual is a main operating document intended for technical maintenance and operating staff The manual contains information about purpose technical details operating principle design and installation of the Axis Jet unit and all its modifications Technical and maintenance staff must have theoretical and practical training in the field of ventilation ...

Страница 3: ...et hands Do not carry out the installation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit ge...

Страница 4: ... WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN PURPOSE DELIVERY SET DESIGNATION KEY Designation example Axis Jet K I 315M 2 4 R U 200 2 Model Jet axial fan Casing type K round Casing insulation _ without sou...

Страница 5: ...2 355 425 1654 1872 Axis Jet KI KI 355 R 467 302 420 482 1954 2202 Axis Jet KI KI 400 R 515 351 460 525 2004 2253 Axis Jet KI KI 450 R 565 351 500 575 2004 2253 Axis Jet KI KI 500 R 603 371 580 620 2004 2290 Axis Jet KI KI 560 R 663 446 620 678 2093 2400 Axis Jet KI KI 630 R 733 550 710 748 2193 2520 TECHNICAL DATA The unit is rated as a Class I electrical appliance Ingress protection rating again...

Страница 6: ...2000 22 5 5 14 3 7 1 2880 1440 25 55 C 55 C Axis Jet KI 315 2 4 R 200 2 200 C 2 h F200 Axis Jet KI 315 2 4 R 300 2 300 C 2 h F300 Axis Jet KI 315 2 4 R 400 2 400 C 2 h F400 Smoke extraction mode once for two hours 355 Unidirectional 1 Axis Jet KI 355 2 U 3 400 50 0 75 5900 36 16 6 2880 25 55 C 55 C Axis Jet KI 355 2 U 200 2 200 C 2 h F200 Axis Jet KI 355 2 U 300 2 300 C 2 h F300 Axis Jet KI 355 2 ...

Страница 7: ...8500 4200 57 14 18 8 9 3 2880 1440 25 55 C 55 C Axis Jet KI 400 2 4 U 200 2 200 C 2 h F200 Axis Jet KI 400 2 4 U 300 2 300 C 2 h F300 Axis Jet KI 400 2 4 U 400 2 400 C 2 h F400 Axis Jet KI 400M 2 4 U 3 400 50 2 2 0 5 9900 4900 77 19 21 9 10 9 2880 1440 25 55 C 55 C Axis Jet KI 400M 2 4 U 200 2 200 C 2 h F200 Axis Jet KI 400M 2 4 U 300 2 300 C 2 h F300 Axis Jet KI 400M 2 4 U 400 2 400 C 2 h F400 Re...

Страница 8: ...0 50 2 5 0 65 12800 6400 106 26 22 4 11 2 2880 1440 25 55 C 55 C Axis Jet KI 450S 2 4 U 200 2 200 C 2 h F200 Axis Jet KI 450S 2 4 U 300 2 300 C 2 h F300 Axis Jet KI 450S 2 4 U 400 2 400 C 2 h F400 Reversible 1 Axis Jet KI 450 2 R 3 400 50 1 5 10100 63 17 6 2880 25 55 C 55 C Axis Jet KI 450 2 R 200 2 200 C 2 h F200 Axis Jet KI 450 2 R 300 2 300 C 2 h F300 Axis Jet KI 450 2 R 400 2 400 C 2 h F400 Ax...

Страница 9: ...00 50 8 2 24500 12200 245 61 27 6 13 8 2880 1440 25 55 C 55 C Axis Jet KI 560M 2 4 U 200 2 200 C 2 h F200 Axis Jet KI 560M 2 4 U 300 2 300 C 2 h F300 Axis Jet KI 560M 2 4 U 400 2 400 C 2 h F400 Reversible 2 Axis Jet KI 560 2 4 R 3 400 50 4 4 1 1 18200 9000 134 33 20 5 10 2 2880 1440 25 55 C 55 C Axis Jet KI 560 2 4 R 200 2 200 C 2 h F200 Axis Jet KI 560 2 4 R 300 2 300 C 2 h F300 Axis Jet KI 560 2...

Страница 10: ...le The grille prevents penetration of objects which may damage the impeller or the fan casing Silencers Sound insulation is achieved by means of cylindrical silencers installed on both sides The casing of the silencers is completely lined with wear resistant mineral wool and perforated sheet The silencer 1 at the inlet is equipped with an aerodynamically optimized inlet nozzle and the silencer 2 a...

Страница 11: ...asteners consider the material of the mounting surface as well as the weigh of the fan refer to the Technical data section Fasteners for fan mounting are not included in the delivery set and should be ordered separately Fasteners for unit mounting should be selected by the service technician WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT MAINTENANCE AND REPAIR BEFORE MOUNTING MA...

Страница 12: ...nal block and the terminal designation label are inside the terminal box The terminal box is installed on the fan casing or on a mounting bracket depending on the particular model Single speed fan wiring diagram Two speed fan wiring diagram running at low speed L1 L3 X1 1 2 3 L3 L1 PE 3 400 V 50 Hz L2 4 PE L2 X1 L3 L1 L2 1 2 3 4 5 6 U1 V1 W1 U2 V2 W2 3 400 V 50 Hz PE PE running at high speed X1 L3...

Страница 13: ...cts on the operation of the driven mechanism Soft start SC starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals limit the motor current regulate the torque Regulation by limiting the current sets the maximum in rush current equal to 300 400 or 250 in some rare instances of the ...

Страница 14: ...protective equipment the higher the chances of success The use of an FC in this case helps solve the problem fundamentally Standard switching equipment automatic circuit breakers contactors and motor starters is not designed to withstand prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of time Using switching equipment with a hig...

Страница 15: ... mounting brackets and remove the casing with the silencers disconnect the casing from the silencer 1 by unscrewing the clamping bolts remove the terminal box cover and disconnect the electric motor cable from the terminal block undo the screws on the casing which secure the motor mounts carefully remove the motor on the mounts from the casing on completing the technical maintenance re install the...

Страница 16: ...nit which successfully passed commutation and load tests and has a technical compliance certificate The selection should be limited to the top five foreign switching equipment manufacturers The fan fails to reach the required rotation speed due to serious overheating of the fan motor Fan motor overloaded Eliminate the overloa Improper fan starting method Use a soft starter or frequency converter t...

Страница 17: ...ation Check the stability of power supply parameters and electric motor operation STORAGE AND TRANSPORTATION REGULATIONS Store the unit in the manufacturer s original packaging box in a dry closed ventilated premise with temperature range 5 40 C and relative humidity up to 70 Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion insulation and sealing def...

Страница 18: ...y repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component The warranty repair does not include routine technical maintenance unit installation dismantling unit setup To bene...

Страница 19: ...ery with the user s manual The warranty terms are acknowledged and accepted Customer s Signature TheAxis Jet KI __________________________________unitisinstalledpursuanttotherequirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provision...

Страница 20: ...www blaubergventilatoren de B114EN 02 ...