The date and time on the control panel must be set correctly (described in the present manual).

• 

The unit operation schedule is programmed for each day of the week individually.

• 

The schedule contains 6 lines with parameters for setting the operating modes within one day. To select the other day of the week, click 

on the day of the week in the upper right corner of the screen.

• 

Each schedule line can contain any time values, but within one day. 

The initial value of the time in the line (the one on the left) should not exceed the finite time interval (the one on the right). Otherwise, 
the difference in these intervals will be negative and the AUTO mode will not work.

• 

If the time intervals of different schedule lines overlap in time, the priority will be given to the line that Is listed lower.

Example:

1st line

   

10:00

 

-

 

12:00

   

1

   

20

2nd line

  

11:00

 

-

 

13:00

   

2

   

20

In the interval from 10:00 to 11:00, the unit will operate at the first speed, and from 11:00 will switch to the second speed, since the lower 
line has a higher priority than the top line.

• 

If there are temporary breaks between different lines of the schedule, the unit will operate in the 

STANDBY

 mode in these time intervals 

(between lines).

• 

If"0" is set in the 

STANDBY

 mode settings, the unit will turn off. If "1" is set in the 

STANDBY

 mode settings, then the unit will operate 

at minimum speed.

Example:

1st line

   

10:00

 

-

 

12:00

   

1

   

20

2nd line

  

13:00

 

-

 

14:00

   

2

   

20

• 

The unit will operate in the 

STANDBY

 mode in the range between 12:00 and 13:00.

20. Date and time

• 

To set the date and time on the control panel, go to the User menu by 

pressing 

 (see para. 5) and then press 

DATE, TIME

 

11

15

01

01

2012

• 

Then adjust the year, month, date, hour and minutes by pressing  

 and 

.

• 

Press 

ENTER

 

 to confirm the set parameter.

• 

To return to the Engineering menu without saving changes, press  

EXIT

 

.

www.blaubergventilatoren.de

S11/S19

17

Содержание S11

Страница 1: ...Sensor Control Panel Sensor control panel EN S11 S19 USER S MANUAL ...

Страница 2: ...intenance and operating staff The manual contains information about the purpose technical details operating principle design and installation of the S11 S19 unit s and all of its their modifications Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construc...

Страница 3: ...s with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE SAFETY REQUIREMENTS Please read the user s manual c...

Страница 4: ...WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN PARAMETER VALUE Ambient temperature C 5 40 Relative humidity 5 80 no condensation Cable cross section mm2 0 25 0 75 Material plastic Cable length m 10 30 Ingress...

Страница 5: ...screws on the panel edge Disassemble the panel by separating the frontal part from the back part Pass the cable into the rectangular opening on the back part of the control panel and fix the panel on the mounting box Connect the cable to the control board and install the frontal part of the panel using the screws MOUNTING AND SET UP RECOMMENDED CROSS SECTIONS OFTHE CABLE CONNECTINGTHE CONTROL PANE...

Страница 6: ...he battery use a new battery only 1 Disconnect the unit from power supply 2 Remove two screws in the bottom part of the casing 3 Pull the top part of the casing aside to allow access to the upper circuit board Replace the battery The control panel uses a CR1220 lithium battery 4 Assemble the control panel in the reverse order If the terminal block wires on the upper circuit board were unplugged ma...

Страница 7: ...mode is active the unit switches to scheduled operation and ignores manual control settings of air flow and temperature provided that the timer is off 3 Manual control settings of air flow and temperature If the TIMER and AUTO modes are off the unit operates in accordance with manual control settings of air flow and temperature Example 1 for unit operation in accordance with control priorities 1 T...

Страница 8: ...the unit slowly increases the speed If the room humidity is lower than the set level the unit slowly decreases the speed In this way the humidity is maintained at the set level The humidity level is set via the Engineering menu see para 14 If the AUTO or TIMER mode is activated the current airflow value is displayed in real time operation no matter of the air flow value set by means of the AIR FLO...

Страница 9: ...ges press EXIT 5 User menu To enter the User menu press MENU in the control panel Main menu The User menu contains basic menu items and functions for parameters setting ENG MENU access to the Engineering menu The menu is password protected AUTO ADJUST scheduled operation setting DATE ANDTIME date and time setting TIMER ADJUST setting time and speed operation on timer basis MOTOR HOURS setting filt...

Страница 10: ... menu press EXIT If you forgot the user defined password see para 11 Password Change press and hold RESET until you hear a long sound signal 20 clicks approximately 20 seconds The default password 1111 is set For navigating in the Engineering menu use the following buttons moving upwards in the list moving downwards in the list select the value from the parameter list return to the User menu www b...

Страница 11: ... the Engineering menu select the TEMPERATURE SENSOR submenu and press ENTER Select a desired sensor type Press ENTER to confirm To return to the Engineering menu without saving changes press EXIT The duct temperature sensor is installed in the supply air duct downstream of the heat exchanger The room temperature sensor is integrated in the control panel 9 Language selection To select the control p...

Страница 12: ...arm season at a temperature above 15 C in the cold season at a temperature below 15 C bypass is closed but it protects the heat exchanger from freezing by opening at a temperature below 3 C in the exhaust air duct downstream of the heat exchanger 2 positive bypass opening for natural ventilation at outdoor temperature above 15 C WARNING It is not recommended to use the manual bypass mode 2 during ...

Страница 13: ...activation of the unit 1 standby mode While in the Standby mode the ventilation unit runs at the first speed at the pre set temperature Press ENTER to confirm To return to the Engineering menu without saving changes press EXIT 13 Display brightness adjustment 50 1 Select the BRIGHTNESS ADJUSTMENT submenu from the Engineering menu and press ENTER Then use the or to set the brightness for the OPERAT...

Страница 14: ...talled The control panel is equipped with a humidity sensor Then use or to set the desired humidity level Press ENTER to confirm To return to the Engineering menu without saving changes press EXIT In the HUMIDITY CONTROL mode the minimum air flow is equal to the air flow at the low speed 15 Error control To receive information regarding the last error select ERROR CONTROL submenu from the Engineer...

Страница 15: ...without saving changes press EXIT The default settings are given in the table below 18 Current temperature review 6 15 20 OFF OFF Select the CURRENTTEMPERATURES item in the Engineering menu and press ENTER The display will show the current temperature sensor readings OUTDOOR readings of the temperature sensor installed outdoors or in the outdoor air duct upstream of the heat exchanger DUCT reading...

Страница 16: ...e When the AUTO mode is active the unit switches to scheduled operation and ignores manual control settings of air flow and temperature provided that the timer is off To set up the AUTO mode press the button to enter the User menu see para 5 and press AUTO ADJUST Select the day to enable the AUTO mode Upon entering the menu the value is set to the current day To change the day press the DAY field ...

Страница 17: ... 20 2nd line 11 00 13 00 2 20 In the interval from 10 00 to 11 00 the unit will operate at the first speed and from 11 00 will switch to the second speed since the lower line has a higher priority than the top line If there are temporary breaks between different lines of the schedule the unit will operate in the STANDBY mode in these time intervals between lines If 0 is set in the STANDBY mode set...

Страница 18: ...ive the unit switches to the timer scheduled operation and ignores the schedule settings AUTO mode and manual control settings AIR FLOW and TEMPERATURE Activation of the TIMER function is confirmed with a tick The timer cannot be activated once the HUMIDITY CONTROL mode is on 01 00 0 20 Use or buttons to set the time air flow and air temperature values Press ENTER to confirm the set parameters To ...

Страница 19: ...by pressing the button see para 5 and press MOTOR HOURS 4000 2569 Use the or buttons to set the filter replacement interval in the MOTOR HOURS window in the SETTING field The OPERATING HOURS window shows the time elapsed from the filter installation Press RESET after replacement of the filter To save the changes and return to the Engineering menu press EXIT CAUTION If the differential pressure sen...

Страница 20: ...etails are stated in the table below The error message appears every 30 seconds until the system emergency cause has been troubleshooted To reset the error alert restart the unit once the malfunction cause has been eliminated If the communication between the panel and the controller fails a message ERP appears in the upper line of the main screen which disappears when the connection is restored ww...

Страница 21: ...aters to the unit This alarm is reversible and the unit must not be restarted When water pressure is detected the unit restarts to operate Install a jumper in case of no water pressure sensor in the units with a water heater TU1 TU2 Break of common power line of the sensor or malfunction of the temperature sensor TU3 TU4 Break of common power line of the sensor or malfunction of the temperature se...

Страница 22: ...rol OFF ON OFF Supply fan off mode OFF ON OFF Humidity sensor selection 2 Bypass operation mode 1 Supply fan off mode Working hours 20 Minute Downtime 5 Minute Switch off temperature 1 С Standby mode setting Air flow rate 0 Temperature 20 С Display brightness adjustment Operation 50 Sleep 1 Humidity setting Duct 50 Room 50 Temperature sensor correction 4 С Timer settings Hours 01 Hour Minutes 00 M...

Страница 23: ...www blaubergventilatoren de S11 S19 23 ...

Страница 24: ...www blaubergventilatoren de B55 6EN 11 ...

Отзывы: