DESIGN AND OPERATING PRINCIPLE

The unit has the following operating principle: warm stale extract air from the room flows into the unit where it is filtered by the extract 
filter, then air flows through the heat exchanger and is exhausted outside by the extract fan.  Cold fresh air from the outside flows into 
the unit, where it is cleaned by the supply filter.  Then the air flows through the heat exchanger and is directed to the room with the 
supply fan.  Heat energy of warm extract air is transferred to clean intake fresh air from the outside and warms it up.  The air flows are fully 
separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of space heating in 
the cold season.

UNIT DESIGN

1

2

3
4

5
6

7

8

9

10

11
13

15

14

12

– cable glands; 

2

 – control unit; 

3

 – bypass damper (except KOMFORT EC S(1)160(-E) models); 

4

 – counter-flow heat exchanger; 

5

 – extract filter; 

6

 – supply filter; 

7

 – supply fan; 

8

 – extract fan; 

9

 – drain pan; 

10

 – drain pipe; 

11

 – extract filter differential pressure switch 

(only for the KOMFORT EC SB 550(-E) S21 units); 

12

 – EVH duct electric preheater connector; 

13

 – ENH duct electric reheater connector;  

14

 – SETUP MODE button (for the units with S21 automation); 

15

 – supply filter differential pressure switch (only for the KOMFORT EC SB 550(-E) S21 

units).

The air handling unit is equipped with a hinged front service panel for repair and maintenance operations. The removable service panel 
design enables to change the service side location. The control unit is accessible for installation and wiring operations through the 
inspection door on top of the unit.  The power cable and ground cable are connected to the control unit via the cable glands.
The bypass damper is open or closed depending on operation mode of the unit.
The KOMFORT EC SB550(-E) units are equipped with differential pressure switches for filter contamination control.  Access to the pressure 
switches is provided through the inlet and outlet spigots.
The difference between the supply and extract air flow temperature leads to condensate generation in the  KOMFORT EC S(1)(B) 160/350/550 
units. Condensate is collected in the drain pan and is removed outside through the drain pipe. 
The KOMFORT EC S(1)(B) 160/350/550-E units are equipped with a heat exchanger with an enthalpy membrane and do not require 
condensate drainage.

Accessories for the unit are available on a separate order.

• 

Humidity sensor. 

The 

FS2

 sensor in the EC KOMFORT EC S(1)(B) 160/350/550(-E)  S21 models is connected to the controller. In the  

 KOMFORT EC S(1)(B) 160/350/550(-E)  S14 models, the 

FS2

 sensor is connected to the terminal block. The 

HR-S

 sensor is connected 

to the controller.  The unit with an installed humidity sensor maintains a set indoor humidity point. As the extract air humidity rises 
above the set point, the system automatically switches to the maximum speed. As the humidity drops down below the set point the 
unit returns to the previous mode.

• 

CO

2

 sensor

 (connected to the controller). Designed for indoor carbon dioxide concentration measurement and respective air capacity 

regulation through the control output signal to the fan. 

• 

VOC sensor

 (connected to the controller). Qualitative assessment of air saturation with contaminants (cigarette smoke, exhaled air, 

solvent and detergent vapours).The sensor sensitivity can be adjusted with regards to the expected maximum level of air pollution. 
Enables on-demand ventilation which results in considerable energy savings as air is exchanged only upon reaching the preset level 
of pollution.

• 

EVH duct preheater 

(for the KOMFORT EC S(1)(B) 160/350/550(-E) S21 units). The heater maintains the duct air temperature at a 

point that prevents the heat exchanger freezing. Heater installation and connection to the unit are described in the heater user’s 
manual.

• 

ENH duct reheater 

(for the KOMFORT EC S(1)(B) 160/350/550(-E) S21 units). The heater maintains a room temperature set by the 

temperature sensor. Heater installation and connection to the unit are described in the heater user’s manual.

www.blaubergventilatoren.de

KOMFOrt EC S(1)(B) 160/350/550(-E) 

7

Содержание KOMFORT EC S 160

Страница 1: ...0 KOMFORT EC S 160 E KOMFORT EC S1 160 KOMFORT EC S1 160 E KOMFORT EC SB 160 KOMFORT EC S1B 160 KOMFORT EC SB 160 E KOMFORT EC S1B 160 E KOMFORT EC SB 350 KOMFORT EC S1B 350 KOMFORT EC SB 350 E KOMFORT EC S1B 350 E KOMFORT EC SB 550 KOMFORT EC SB 550 E ...

Страница 2: ...ns 12 Technical maintenance 15 Storage and transportation regulations 16 Possible reasons and troubleshooting 16 Manufacturer s warranty 17 Certificate of acceptance 19 Seller information 19 Installation certificate 19 Warranty card 19 SAFETY REQUIREMENTS All user s manual requirements as well as the provisions of all the applicable local and national construction electrical and technical norms an...

Страница 3: ...Do not close or block the intake or extract vents in order to ensure the efficient air flow Do not sit on the unit and do not put objects on it This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a ...

Страница 4: ...ating energy by means of energy recovery the unit is an important element of energy efficient premises The unit is a component part and is not designed for stand alone operation It is rated for continuous operation Transported air must not contain any flammable or explosive mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favo...

Страница 5: ...xchanger type Counter flow Heat exchanger material Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane SEC class A A A A A A A A A A A A A A The KOMFORT EC S 1 B 160 350 550 E units are equipped with an enthalpy heat exchanger and do not requ...

Страница 6: ...70 690 590 640 388 143 KOMFORT EC SB 160 E 125 18 340 330 665 580 600 388 143 KOMFORT EC S1B 160 E 125 18 380 370 710 620 640 388 143 KOMFORT EC SB 350 E 160 18 600 583 760 675 730 426 230 KOMFORT EC S1B 350 E 160 18 480 470 760 675 730 426 200 KOMFORT EC SB 550 E 200 18 730 720 760 675 823 498 288 www blaubergventilatoren de KOMFORT EC S 1 B 160 350 550 E 6 ...

Страница 7: ... through the inlet and outlet spigots Thedifferencebetweenthesupplyandextractairflowtemperatureleadstocondensategenerationinthe KOMFORTECS 1 B 160 350 550 units Condensate is collected in the drain pan and is removed outside through the drain pipe The KOMFORT EC S 1 B 160 350 550 E units are equipped with a heat exchanger with an enthalpy membrane and do not require condensate drainage Accessories...

Страница 8: ...th the heat exchanger The temperature of the air is not changed after passing through the heat exchanger INTAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR Back side view Heat exchanger freeze protection frost danger appears when the extract air temperature downstream of the heat exchanger is lower than 5 C and intake air temperature upstream of the heat exchanger is lower than 3 C for units with prehe...

Страница 9: ...TAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR Left hand service side INTAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR Right hand service side Remove the hinge stopper Release the latches disconnect the ground cable and remove the service panel Remove the latches and move them to the opposite side Remove the back panel by undoing the three screws hidden under plastic plugs www blaubergventilatoren de KO...

Страница 10: ...cess to the service panel for maintenance and service operations The unit should be mounted strictly horizontally in the longitudinal and transverse planes In case of non compliance unit s casing distortion and operation disturbance will occur Unit wall mounting Unit floor mounting Dowels for wall mounting are not included in the delivery set and should be ordered separately While choosing dowels ...

Страница 11: ...move the plug in the drain pan Install the drain pipe from the delivery set into the hole then connect the drain pipe to the sewage system using the SFK 20x32 U trap kit available upon separate order Make sure the U trap is always filled with water The pipe slope downwards must be at least 3 1 2 3 4 min 3 1 drain pipe 2 U trap 3 drain hose 4 sewage system www blaubergventilatoren de KOMFORT EC S 1...

Страница 12: ... to 1 220 240 V 50 60 Hz power mains The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit in case of overload or short circuit The circuit breaker installation place must provide quick access for emergency shutdown of the unit The trip current of the automatic circuit breaker must exceed the maximum current consum...

Страница 13: ...D X1 L SQ PE N NO NO A B NC C C C NO C NO C 24V 24V L 2 N 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0 10V GND А В 24V 1 2 PK1 1 2 1 2 P1 1 2 1 2 1 2 CCU Boost 1 2 SM1 1 2 SM2 U U CO2 GND 0 10V 24V Brown Yellow Green White Power input 230 VAC Designation Name Model Wire Note SM1 Supply air damper actuator NO 2 x 0 75 mm2 3A 30DC 250 AC SM2 Extract air damper actuator NO 2 x 0 75 mm2 3A 30DC...

Страница 14: ... SM2 Extract air damper actuator NO 2 x 0 75 mm2 3A 30VDC 250 AC РК1 Contact from fire alarm panel NC 2 x 0 75 mm2 CCU CCU control NO 2 x 0 75 mm2 3A 30VDC 250 AC P1 External control panel 4 x 0 25 mm2 Boost On Off contacts for the Boost mode NO 2 x 0 75 mm2 CO2 External CO2 sensor NO 3 x 0 75 mm2 Is not included in the delivery set The U supply voltage of the SM1 SM2 external dampers is selected ...

Страница 15: ... the filters some dust may accumulate inside the fans and reduce the fan performance and supply air flow Fans should be cleaned by the service technician 4 Condensate drainage system maintenance 4 times per year The condensate drainage drain line may get clogged by dirt and dust particles contained in the exhaust air Check the drain line operation by filling the drain pan under the unit with water...

Страница 16: ...r duct pipe flanges Install anti vibration connectors Water leakage only for the KOMFORT EC S 1 B 160 350 550 units The drainage system is soiled damaged or installed incorrectly Clean the drain line Check the drain line slope angle Make sure that the U trap is filled with water and the drain pipes are frost protected If troubleshooting steps have failed contact the Seller of the product In case o...

Страница 17: ...ir the user must provide the unit the user s manual with the purchase date stamp and the payment paperwork certifying the purchase The unit model must comply with the one stated in the user s manual Contact the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manu...

Страница 18: ...www blaubergventilatoren de KOMFORT EC S 1 B 160 350 550 E 18 ...

Страница 19: ...is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standards The unit operates normally as intended by th...

Страница 20: ...www blaubergventilatoren de B203EN 04 ...

Отзывы: