MOUNTING SEQUENCE
1.
Cut off power supply.
QF
2.
Mark and drill the holes on the mounting surface for the fan mounting.
3.
Fix the KS-ISK mounting angle brackets on a mounting bracket using
appropriate fasteners, for example, expansion anchors.
4.
Install the fan on the KS-ISK mounting brackets and fix it using
appropriate fasteners.
5.
Install accessories, i.e. install a backdraft damper into the fan spigot.
6.
Connect air ducts to the fan and fix those with clamps (available upon
separate order).
The fan is designed for connection to round air ducts on both sides of the
fan.
The special fixing brackets in the fan casing enable selecting the most
suitable fan installation position.
If the fan is connected through the flexible anti-vibration connectors the
fan must be secured to a mounting surface with supports, hanger brackets
or brackets.
The air motion direction in the system must match the pointer on the fan
casing.
Install the fan to ensure sufficient and quick access for servicing and repair
operations.
The fan must be grounded.
To reduce air turbulence related pressure losses connect a straight air duct
to the fan of the length equal to min. 1 air duct diameter on the intake side
and min. 3 air duct diameter on the exhaust side.
Power is supplied either through the external terminal box.
Mounting of the fan on the wall with the KS-ISK mounting angle brackets
is shown in fig. 3 (available upon separate order).
MOUNTING AND OPERATION GUIDELINES
WARNING
Before starting mounting:
Read carefully the fan mounting, start-up, operation and servicing instructions;
Check the fan for possible transport damages.
Follow the safety regulations during the fan start-up and operations.