DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED
ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER
CAREFUL READING OF THE PRESENT USER’S MANUAL. THE RATED ELECTRICAL
PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID
THE WARRANTY.
• The unit is rated for connection to 1~230 V/50 Hz power mains.
• The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual wire cross section selection
must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and
installation method.
• The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric
circuit in case of overload or short-circuit. The circuit breaker installation place must provide quick access for emergency shutdown
of the unit. The trip current of the automatic circuit breaker
QF
must exceed the maximum current consumption of the unit (refer
to the technical data table). The recommended trip current of the circuit breaker is the next current in the standard trip current row
following the maximum current of the connected unit. The automatic circuit breaker is not included in the delivery set.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED
AND WILL VOID THE WARRANTY.
The recommended cross section of conductors (cables, wires) is 0.75 mm
2
.
The recommended circuit breaker nominal current should be not less than 1 A.
WIRING DIAGRAMS
Iso Box-F(R)
Iso Box-F(R) V2 Duo double-speed fan
Electrostatic filter
X3
L
L
QF* XP*
PE
N
N
PE
C
M
~230 V
50 Hz
X3
L1
L2
L
QF* XP*
PE
N
PE
N
S1
C
M
Low
High
~230 V
50 Hz
X1
PE
N
PE
QF* XP*
L
LF
N
L
~230 V
50 Hz
*Purchased separately.
CONTROL
The speed of the double-speed fan is switched (Low/High) at the stage of its connection to power mains according to the wiring diagram.
The electrostatic filter is switched on/off by means of a switch on the fan casing.