www.blaubergventilatoren.de
5
Box-D
Fig. 2. Overall dimensions
TECHNICAL DATA
Table 1. Technical data
Table 2. Overall dimensions
MOUNTING AND OPERATION GUIDELINES
The fan is mounted between the load-bearing ceiling and the false ceiling
using the mounting brackets from the delivery set, Fig. 3. The distance from the
mounting point of the mounting brackets to the false ceiling is 165-390 mm.
The fl exible air duct of the matching diameter is fi xed on the fan spigot with
a clamp.
The air motion direction in the system must match the pointer on the fan
casing.
The fan installation place must ensure suffi
cient and quick access for servicing
and repair operations.
The fan must be reliably grounded.
Shut off power supply prior to starting the fan mounting.
WARNING
Before starting mounting:
read carefully the operation manual;
check the fan for possible transport damages;
Follow the safety regulations during the fan start-up and operation;
Model
Dimensions [mm]
Weight [kg]
ØD
B
H
L
Box-D 100 L
100
240
160
305
3.4
Box-D 100
100
240
160
305
3.4
Box-D 125 L
125
240
160
305
3.4
Box-D 125
125
240
160
305
3.4
Box-D 150
149
355
180
419
6.5
Parameters
Box-D 100 L
Box-D 100
Box-D 125 L
Box-D 125
Box-D 150
Voltage, 50-60 Hz [V]
1~ 230
50 Hz
1~ 230
60 Hz
1~ 230
50 Hz
1~ 230
60 Hz
1~ 230
50 Hz
1~ 230
60 Hz
1~ 230
50 Hz
1~ 230
60 Hz
1~ 230
50 Hz
1~ 230
60 Hz
Power [W]
56
58
61
79
56
58
61
81
112
136
Current [A]
0.34
0.35
0.26
0.35
0.34
0.35
0.26
0.36
0.5
0.6
Max. air fl ow [m
3
/h] 190
205
240
250
225
240
310
320
485
531
RPM
2300
2570
2500
2730
2300
2570
2500
2740
2465
2550
Sound pressure level at 3 m distance
[dB(A)]
42
43
47
48
43
44
48
49
52
53
Max. transported air temperature [°C]
-25 +45
-25 +50
-25 +45
-25 +50
-25 +50
Ingress Protection Rating
IP X4
IP X4
IP X4
IP X4
IP X4
Содержание Box-D 100
Страница 1: ...Box D EXHAUST CENTRIFUGAL FAN OPERATION MANUAL EN...
Страница 12: ...www blaubergventilatoren de Box D v 3 2 EN...