Mounting in case of no ductwork upstream of the fan

If the ductwork is not available at the fan inlet, the inlet cone VK-AF must 
be installed to improve aerodynamic parameters of the air flow.

Obstructed space installation

To ensure normal operation of the fan in an obstructed space make sure 
to provide for a sufficient distance between the inlet and outlet flanges 
and the floor, walls, bulky equipment and obstacles.

H ≥ D

≥ 

D

D

H ≥ D

≥ 

D

D

Mounting in case of no ductwork downstream of the fan

If the axial fan is the terminal device of the ventilation system (i.e. there 
is no downstream ducting), the unit must be equipped with a diffuser to 
reduce the air flow velocity and the fan dynamic pressure. Reduction of 
the air discharge velocity results in a significant reduction of shock losses 
which are proportional to the square of velocity decrement.
Installation of a downstream contractor is not recommended.

Installation near bends

To install the fan directly downstream of a bend (elbow) use a curved section with a large bending radius or an array of internal guide vanes.

•  When installing the fan in an air duct, connection to the air ducts is made by means of flanges.
•  The O-AF carriers are used for mounting the fans to the floor, walls or ceiling. The carriers are fixed to the ceiling by means of the threaded expansion 

anchors and mounting studs. Fix threaded expansion anchors to attach the carriers to the floor or to the wall. 

•  The carriers and the fasteners are not included in the delivery set and are available as specially ordered accessories. Selection of the fasteners must be 

based on material of a mounting surface and the fan weight. For details, please refer to the Technical data. The fastener selection must be performed 
by a qualified technician.

After installing the unit, you need to make sure that the fan impeller rotates freely.

www.blaubergventilatoren.de

Axis-p

10

Содержание AXIS-P Series

Страница 1: ...Axial pressurisation fan USER S MANUAL EN Axis P...

Страница 2: ...ny reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this publicat...

Страница 3: ...ing the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation o...

Страница 4: ...power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disc...

Страница 5: ...stems with high air flow rates THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INST...

Страница 6: ...60 40 C T tropical climate 10 50 C M maritime moderately cold climate 40 40 C O general climatic modification except maritime climate 60 50 C OM general maritime climatic modification 40 40 C V unive...

Страница 7: ...al box Casing modification with a terminal box d n holes d n holes MODEL DIMENSIONS MM L D D1 D2 d n B Axis P400 350 450 400 450 490 8 12 480 Axis P450 350 450 550 450 500 540 8 12 525 Axis P500 350 4...

Страница 8: ...quare cage rotor installed inside the casing The fan casing modifications depend on the electrical cable connection options The cable is connected to the electric motor terminal box via a cable gland...

Страница 9: ...The length of the straight duct section downstream of the fan must be 1 5 2 D Installation of shorter air ducts may result in insufficient air pressure and air flow The flexible joints EVAF AF are re...

Страница 10: ...crement Installation of a downstream contractor is not recommended Installation near bends To install the fan directly downstream of a bend elbow use a curved section with a large bending radius or an...

Страница 11: ...on The fan must be integrated into a ventilation or smoke extraction system with an automatic control system The fan motor is rated for connection to 400 V 50 60 Hz three phase alternating current Con...

Страница 12: ...smooth out the inrush the high startup torque has no adverse effects on the operation of the driven mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the moto...

Страница 13: ...ces of success The use of an FC in this case helps solve the problem fundamentally Standard switching equipment automatic circuit breakers contactors and motor starters is not designed to withstand pr...

Страница 14: ...rt No power supply Check the mains switch Check the electrical connections against the wiring diagram Jammed motor Carefully check the fan impeller for possible seizure and eliminate it if necessary I...

Страница 15: ...place the fan with a unit of proper standard size The fan supplies less air than expected Wrong calculation of the ventilation network and wrong selection of the fan Re calculate the network parameter...

Страница 16: ...handling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mecha...

Страница 17: ...nded use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component The warranty...

Страница 18: ...www blaubergventilatoren de Axis P 18...

Страница 19: ...______ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Sig...

Страница 20: ...www blaubergventilatoren de B118EN 05...

Отзывы: